The controller C(s) = 2(s + 2)/s drives the plant G(s) = 5/(s(s + 4)) in a unity-feedback loop. What is the system type N of the loop?
Steady-state error & PID control worksheet with answers
A proportional controller K = 5 drives the plant G(s) = 2/(s + 10) in a unity-feedback loop. A step of size 5 is applied. Find the final value of the output y(∞).
The parabolic input r(t) = 10·t²/2 is applied to a unity-feedback loop with G(s) = 20(s + 5)/(s²(s + 2)). Find the steady-state error ess.
A process G(s) = 4/(1s + 1) is controlled by a proportional gain K = 1 in a unity-feedback loop. Find the steady-state error ess for a step, as a percentage of the step size.
A PI controller C(s) = Kp + Ki/s drives the plant G(s) = 1/(s + 5) in a unity-feedback loop. The closed loop must have ωₙ = 6 rad/s and ζ = 0.5. Find the proportional gain Kp.
A proportional controller K drives the plant G(s) = 1/(s(s + 10)) in a unity-feedback loop. Find the gain K that gives the closed loop a damping ratio ζ = 0.8.
Answer key
- 1. N = 2
- 2. y(∞) = 2.5
- 3. ess = 0.2
- 4. ess = 20 %
- 5. Kp = 1
- 6. K = 39.06