The controller C(s) = 2(s + 1)/s drives the plant G(s) = 1/(s + 10) in a unity-feedback loop. What is the system type N of the loop?
Steady-state error & PID control worksheet with answers
A proportional controller K = 5 drives the plant G(s) = 2/(s + 2) in a unity-feedback loop. A step of size 10 is applied. Find the final value of the output y(∞).
The parabolic input r(t) = 0.5·t²/2 is applied to a unity-feedback loop with G(s) = 20(s + 4)/(s²(s + 2)). Find the steady-state error ess.
A ramp r(t) = 3t is applied to a unity-feedback loop with G(s) = 50/(s(s + 2)(s + 5)). Find the steady-state error ess.
A proportional controller K = 20 drives the plant G(s) = 1/(s(s + 6)) in a unity-feedback loop. Find the 2 % settling time ts of the step response, using ts ≈ 4/(ζωₙ).
A PD controller C(s) = 20 + Kd·s drives the plant G(s) = 1/(s(s + 2)) in a unity-feedback loop. Find the derivative gain Kd that gives the closed loop a damping ratio ζ = 0.6.
Answer key
- 1. N = 1
- 2. y(∞) = 8.333
- 3. ess = 0.0125
- 4. ess = 0.6
- 5. ts = 1.333 s
- 6. Kd = 3.367 s