A balanced Y-connected load has an impedance of 6 + j8 Ω per phase. It is supplied from a balanced three-phase source with a line-to-line voltage of 400 V. Find the magnitude of the line current IL.
Three-phase power worksheet with answers
A balanced Δ-connected load has an impedance of 18 + j24 Ω per phase. It is supplied from a balanced three-phase source with a line-to-line voltage of 690 V. Find the magnitude of the phase current Iph flowing through each impedance.
A three-phase induction motor delivers 11 kW of mechanical output power at full load. At this load its efficiency is 93% and its power factor is 0.82 lagging. The supply has a line-to-line voltage of 690 V. Find the line current IL.
A three-phase induction motor delivers 15 kW of mechanical output power at full load. At this load its efficiency is 90% and its power factor is 0.9 lagging. The supply has a line-to-line voltage of 400 V. Find the line current IL.
A balanced three-phase load takes 150 kW at a power factor of 0.75 lagging from a 690 V (line-to-line), 50 Hz supply. A three-phase capacitor bank in parallel with the load must raise the overall power factor to 0.95 lagging. The real power stays the same. Find the total reactive power QC the capacitor bank must supply, in kvar.
A balanced three-phase load takes 150 kW at a power factor of 0.72 lagging from a 690 V (line-to-line), 50 Hz supply. A three-phase capacitor bank in parallel with the load must raise the overall power factor to 0.95 lagging. The real power stays the same. The capacitors are connected in Δ. Find the capacitance Cph of each capacitor in µF.
Answer key
- 1. IL = 23.09 A
- 2. Iph = 23 A
- 3. IL = 12.07 A
- 4. IL = 26.73 A
- 5. QC = 82.98 kvar
- 6. Cph = 212.3 µF
Full step-by-step solutions: practise this topic on examproblems.com.