A balanced Y-connected load has an impedance of 5 + j12 Ω per phase. It is supplied from a balanced three-phase source with a line-to-line voltage of 480 V. Find the magnitude of the line current IL.
Three-phase power worksheet with answers
A balanced Y-connected load has an impedance of 9 + j12 Ω per phase. It is supplied from a balanced three-phase source with a line-to-line voltage of 208 V. Find the magnitude of the line current IL.
A balanced Δ-connected load with an impedance of 18 + j24 Ω per phase is connected to a balanced three-phase supply with a line-to-line voltage of 400 V. Find the total real power P absorbed by the load in kW.
A balanced Y-connected load with an impedance of 15 + j20 Ω per phase is connected to a balanced three-phase supply with a line-to-line voltage of 208 V. Find the total real power P absorbed by the load in kW.
A balanced three-phase load takes 150 kW at a power factor of 0.7 lagging from a 400 V (line-to-line), 60 Hz supply. A three-phase capacitor bank in parallel with the load must raise the overall power factor to 0.92 lagging. The real power stays the same. The capacitors are connected in Δ. Find the capacitance Cph of each capacitor in µF.
A balanced three-phase load takes 50 kW at a power factor of 0.65 lagging from a 400 V (line-to-line), 60 Hz supply. A three-phase capacitor bank in parallel with the load must raise the overall power factor to 0.92 lagging. The real power stays the same. The capacitors are connected in Y. Find the capacitance Cph of each capacitor in µF.
Answer key
- 1. IL = 21.32 A
- 2. IL = 8.006 A
- 3. P = 9.6 kW
- 4. P = 1.038 kW
- 5. Cph = 492.6 µF
- 6. Cph = 616 µF