A balanced Δ-connected load has an impedance of 24 + j7 Ω per phase. It is supplied from a balanced three-phase source with a line-to-line voltage of 400 V. Find the magnitude of the phase current Iph flowing through each impedance.
Three-phase power worksheet with answers
A balanced Δ-connected load has an impedance of 16 + j12 Ω per phase. It is supplied from a balanced three-phase source with a line-to-line voltage of 480 V. Find the magnitude of the line current IL.
A three-phase induction motor delivers 45 kW of mechanical output power at full load. At this load its efficiency is 94% and its power factor is 0.85 lagging. The supply has a line-to-line voltage of 480 V. Find the line current IL.
A balanced Y-connected load with an impedance of 8 + j6 Ω per phase is connected to a balanced three-phase supply with a line-to-line voltage of 400 V. Find the total real power P absorbed by the load in kW.
A balanced three-phase load takes 150 kW at a power factor of 0.7 lagging from a 415 V (line-to-line), 50 Hz supply. A three-phase capacitor bank in parallel with the load must raise the overall power factor to 0.92 lagging. The real power stays the same. Find the total reactive power QC the capacitor bank must supply, in kvar.
A balanced three-phase load takes 300 kW at a power factor of 0.75 lagging from a 400 V (line-to-line), 60 Hz supply. A three-phase capacitor bank in parallel with the load must raise the overall power factor to 0.95 lagging. The real power stays the same. Find the total reactive power QC the capacitor bank must supply, in kvar.
Answer key
- 1. Iph = 16 A
- 2. IL = 41.57 A
- 3. IL = 67.74 A
- 4. P = 12.8 kW
- 5. QC = 89.13 kvar
- 6. QC = 166 kvar
Full step-by-step solutions: practise this topic on examproblems.com.