A balanced Δ-connected load has an impedance of 4 + j3 Ω per phase. It is supplied from a balanced three-phase source with a line-to-line voltage of 480 V. Find the magnitude of the line current IL.
Three-phase power worksheet with answers
A balanced Y-connected load has an impedance of 6 + j8 Ω per phase. It is supplied from a balanced three-phase source with a line-to-line voltage of 400 V. Find the magnitude of the line current IL.
A three-phase induction motor delivers 55 kW of mechanical output power at full load. At this load its efficiency is 95% and its power factor is 0.84 lagging. The supply has a line-to-line voltage of 400 V. Find the line current IL.
A three-phase induction motor delivers 90 kW of mechanical output power at full load. At this load its efficiency is 90% and its power factor is 0.85 lagging. The supply has a line-to-line voltage of 690 V. Find the line current IL.
A balanced three-phase load takes 250 kW at a power factor of 0.7 lagging from a 480 V (line-to-line), 50 Hz supply. A three-phase capacitor bank in parallel with the load must raise the overall power factor to 0.92 lagging. The real power stays the same. The capacitors are connected in Y. Find the capacitance Cph of each capacitor in µF.
A balanced three-phase load takes 50 kW at a power factor of 0.75 lagging from a 480 V (line-to-line), 50 Hz supply. A three-phase capacitor bank in parallel with the load must raise the overall power factor to 0.92 lagging. The real power stays the same. The capacitors are connected in Δ. Find the capacitance Cph of each capacitor in µF.
Answer key
- 1. IL = 166.3 A
- 2. IL = 23.09 A
- 3. IL = 99.48 A
- 4. IL = 98.44 A
- 5. Cph = 2052 µF
- 6. Cph = 105 µF