Three-phase power worksheet with answers

Free printable Three-phase power worksheet: 6 problems from easy to exam level, with an answer key. Print it or save it as a PDF.

For teachers: free to print, copy and use in class. Every new worksheet has new values and its own answer key. A link to ExamProblems on your course page is appreciated.

Name: ____________________   Date: ____________

1.Easy
ABCVL​ = 415 VIL​ = ?Z = 20 + j15 Ωper phase

A balanced Δ-connected load has an impedance of 20 + j15 Ω per phase. It is supplied from a balanced three-phase source with a line-to-line voltage of 415 V. Find the magnitude of the line current IL.

VL = 415 VZ = 20 + j15 Ω per phase
IL = A
2.Easy
ABCVL​ = 208 VZ = 9 + j12 Ωper phase

A balanced Δ-connected load has an impedance of 9 + j12 Ω per phase. It is supplied from a balanced three-phase source with a line-to-line voltage of 208 V. Find the magnitude of the phase current Iph flowing through each impedance.

VL = 208 VZ = 9 + j12 Ω per phase
Iph = A
3.Medium
ABCVL​ = 415 VZ = 24 + j18 Ωper phase

A balanced Δ-connected load with an impedance of 24 + j18 Ω per phase is connected to a balanced three-phase supply with a line-to-line voltage of 415 V. Find the total real power P absorbed by the load in kW.

VL = 415 VZ = 24 + j18 Ω per phase
P = kW
4.Medium
ABCVL​ = 480 VIL​ = ?M22 kW, η = 91%cos φ = 0.8

A three-phase induction motor delivers 22 kW of mechanical output power at full load. At this load its efficiency is 91% and its power factor is 0.8 lagging. The supply has a line-to-line voltage of 480 V. Find the line current IL.

Pout = 22 kWη = 91%cos φ = 0.8VL = 480 V
IL = A
5.Hard
P = 60 kWφ1​S1​Q2​QC​

A balanced three-phase load takes 60 kW at a power factor of 0.75 lagging from a 480 V (line-to-line), 50 Hz supply. A three-phase capacitor bank in parallel with the load must raise the overall power factor to 0.98 lagging. The real power stays the same. The capacitors are connected in Y. Find the capacitance Cph of each capacitor in µF.

P = 60 kWpf1 = 0.75pf2 = 0.98VL = 480 Vf = 50 Hz
Cph = µF
6.Hard
P = 60 kWφ1​S1​Q2​QC​

A balanced three-phase load takes 60 kW at a power factor of 0.7 lagging from a 480 V (line-to-line), 50 Hz supply. A three-phase capacitor bank in parallel with the load must raise the overall power factor to 0.95 lagging. The real power stays the same. The capacitors are connected in Y. Find the capacitance Cph of each capacitor in µF.

P = 60 kWpf1 = 0.7pf2 = 0.95VL = 480 Vf = 50 Hz
Cph = µF

Answer key

  1. 1. IL = 28.75 A
  2. 2. Iph = 13.87 A
  3. 3. P = 13.78 kW
  4. 4. IL = 36.35 A
  5. 5. Cph = 562.7 µF
  6. 6. Cph = 573.2 µF