A balanced Y-connected load has an impedance of 9 + j12 Ω per phase. It is supplied from a balanced three-phase source with a line-to-line voltage of 415 V. Find the magnitude of the line current IL.
Three-phase power worksheet with answers
A balanced Y-connected load has an impedance of 18 + j24 Ω per phase. It is supplied from a balanced three-phase source with a line-to-line voltage of 208 V. Find the magnitude of the line current IL.
A balanced Y-connected load with an impedance of 15 + j20 Ω per phase is connected to a balanced three-phase supply with a line-to-line voltage of 480 V. Find the total real power P absorbed by the load in kW.
A three-phase induction motor delivers 37 kW of mechanical output power at full load. At this load its efficiency is 88% and its power factor is 0.84 lagging. The supply has a line-to-line voltage of 400 V. Find the line current IL.
A balanced three-phase load takes 300 kW at a power factor of 0.78 lagging from a 415 V (line-to-line), 50 Hz supply. A three-phase capacitor bank in parallel with the load must raise the overall power factor to 0.98 lagging. The real power stays the same. Find the total reactive power QC the capacitor bank must supply, in kvar.
A balanced three-phase load takes 50 kW at a power factor of 0.7 lagging from a 480 V (line-to-line), 50 Hz supply. A three-phase capacitor bank in parallel with the load must raise the overall power factor to 0.9 lagging. The real power stays the same. Find the total reactive power QC the capacitor bank must supply, in kvar.
Answer key
- 1. IL = 15.97 A
- 2. IL = 4.003 A
- 3. P = 5.53 kW
- 4. IL = 72.25 A
- 5. QC = 179.8 kvar
- 6. QC = 26.79 kvar