Three-phase power worksheet with answers

Free printable Three-phase power worksheet: 6 problems from easy to exam level, with an answer key. Print it or save it as a PDF.

For teachers: free to print, copy and use in class. Every new worksheet has new values and its own answer key. A link to ExamProblems on your course page is appreciated.

Name: ____________________   Date: ____________

1.Easy
ABCVL​ = 415 VIL​ = ?Z = 9 + j12 Ωper phase

A balanced Δ-connected load has an impedance of 9 + j12 Ω per phase. It is supplied from a balanced three-phase source with a line-to-line voltage of 415 V. Find the magnitude of the line current IL.

VL = 415 VZ = 9 + j12 Ω per phase
IL = A
2.Easy
ABCVL​ = 600 VIL​ = ?NZ = 12 + j9 Ωper phase

A balanced Y-connected load has an impedance of 12 + j9 Ω per phase. It is supplied from a balanced three-phase source with a line-to-line voltage of 600 V. Find the magnitude of the line current IL.

VL = 600 VZ = 12 + j9 Ω per phase
IL = A
3.Medium
ABCVL​ = 208 VZ = 12 + j9 Ωper phase

A balanced Δ-connected load with an impedance of 12 + j9 Ω per phase is connected to a balanced three-phase supply with a line-to-line voltage of 208 V. Find the total real power P absorbed by the load in kW.

VL = 208 VZ = 12 + j9 Ω per phase
P = kW
4.Medium
ABCVL​ = 400 VIL​ = 120 Acos φ = 0.7lagging

A balanced three-phase load draws a line current of 120 A from a supply with a line-to-line voltage of 400 V. The power factor is 0.7 lagging. Find the total real power P drawn by the load in kW.

VL = 400 VIL = 120 Acos φ = 0.7
P = kW
5.Hard
P = 100 kWφ1​S1​Q2​QC​

A balanced three-phase load takes 100 kW at a power factor of 0.72 lagging from a 480 V (line-to-line), 50 Hz supply. A three-phase capacitor bank in parallel with the load must raise the overall power factor to 0.92 lagging. The real power stays the same. The capacitors are connected in Δ. Find the capacitance Cph of each capacitor in µF.

P = 100 kWpf1 = 0.72pf2 = 0.92VL = 480 Vf = 50 Hz
Cph = µF
6.Hard
P = 150 kWφ1​S1​Q2​QC​ = ?

A balanced three-phase load takes 150 kW at a power factor of 0.72 lagging from a 415 V (line-to-line), 60 Hz supply. A three-phase capacitor bank in parallel with the load must raise the overall power factor to 0.92 lagging. The real power stays the same. Find the total reactive power QC the capacitor bank must supply, in kvar.

P = 150 kWpf1 = 0.72pf2 = 0.92VL = 415 Vf = 60 Hz
QC = kvar

Answer key

  1. 1. IL = 47.92 A
  2. 2. IL = 23.09 A
  3. 3. P = 6.922 kW
  4. 4. P = 58.2 kW
  5. 5. Cph = 247.7 µF
  6. 6. QC = 80.68 kvar

Full step-by-step solutions: practise this topic on examproblems.com.