A balanced Δ-connected load has an impedance of 24 + j7 Ω per phase. It is supplied from a balanced three-phase source with a line-to-line voltage of 480 V. Find the magnitude of the phase current Iph flowing through each impedance.
Three-phase power worksheet with answers
A balanced Y-connected load has an impedance of 12 + j5 Ω per phase. It is supplied from a balanced three-phase source with a line-to-line voltage of 600 V. Find the magnitude of the line current IL.
A balanced three-phase load draws a line current of 50 A from a supply with a line-to-line voltage of 690 V. The power factor is 0.9 lagging. Find the total real power P drawn by the load in kW.
A balanced three-phase load draws a line current of 75 A from a supply with a line-to-line voltage of 415 V. The power factor is 0.95 lagging. Find the total real power P drawn by the load in kW.
A balanced three-phase load takes 200 kW at a power factor of 0.72 lagging from a 480 V (line-to-line), 60 Hz supply. A three-phase capacitor bank in parallel with the load must raise the overall power factor to 0.92 lagging. The real power stays the same. Find the total reactive power QC the capacitor bank must supply, in kvar.
A balanced three-phase load takes 50 kW at a power factor of 0.78 lagging from a 690 V (line-to-line), 60 Hz supply. A three-phase capacitor bank in parallel with the load must raise the overall power factor to 0.9 lagging. The real power stays the same. Find the total reactive power QC the capacitor bank must supply, in kvar.
Answer key
- 1. Iph = 19.2 A
- 2. IL = 26.65 A
- 3. P = 53.78 kW
- 4. P = 51.21 kW
- 5. QC = 107.6 kvar
- 6. QC = 15.9 kvar