A balanced Δ-connected load has an impedance of 20 + j15 Ω per phase. It is supplied from a balanced three-phase source with a line-to-line voltage of 415 V. Find the magnitude of the line current IL.
Three-phase power worksheet with answers
A balanced Y-connected load has an impedance of 16 + j12 Ω per phase. It is supplied from a balanced three-phase source with a line-to-line voltage of 208 V. Find the magnitude of the line current IL.
A three-phase induction motor delivers 22 kW of mechanical output power at full load. At this load its efficiency is 92% and its power factor is 0.85 lagging. The supply has a line-to-line voltage of 690 V. Find the line current IL.
A balanced Y-connected load with an impedance of 20 + j15 Ω per phase is connected to a balanced three-phase supply with a line-to-line voltage of 480 V. Find the total real power P absorbed by the load in kW.
A balanced three-phase load takes 250 kW at a power factor of 0.7 lagging from a 400 V (line-to-line), 50 Hz supply. A three-phase capacitor bank in parallel with the load must raise the overall power factor to 0.95 lagging. The real power stays the same. Find the total reactive power QC the capacitor bank must supply, in kvar.
A balanced three-phase load takes 200 kW at a power factor of 0.72 lagging from a 690 V (line-to-line), 50 Hz supply. A three-phase capacitor bank in parallel with the load must raise the overall power factor to 0.9 lagging. The real power stays the same. The capacitors are connected in Δ. Find the capacitance Cph of each capacitor in µF.
Answer key
- 1. IL = 28.75 A
- 2. IL = 6.004 A
- 3. IL = 23.54 A
- 4. P = 7.373 kW
- 5. QC = 172.9 kvar
- 6. Cph = 213.7 µF
Full step-by-step solutions: practise this topic on examproblems.com.