A balanced Δ-connected load has an impedance of 20 + j15 Ω per phase. It is supplied from a balanced three-phase source with a line-to-line voltage of 600 V. Find the magnitude of the phase current Iph flowing through each impedance.
Three-phase power worksheet with answers
A balanced Y-connected load has an impedance of 20 + j15 Ω per phase. It is supplied from a balanced three-phase source with a line-to-line voltage of 600 V. Find the magnitude of the line current IL.
A balanced Y-connected load with an impedance of 12 + j5 Ω per phase is connected to a balanced three-phase supply with a line-to-line voltage of 400 V. Find the total real power P absorbed by the load in kW.
A balanced Y-connected load with an impedance of 24 + j7 Ω per phase is connected to a balanced three-phase supply with a line-to-line voltage of 415 V. Find the total real power P absorbed by the load in kW.
A balanced three-phase load takes 250 kW at a power factor of 0.75 lagging from a 690 V (line-to-line), 50 Hz supply. A three-phase capacitor bank in parallel with the load must raise the overall power factor to 0.98 lagging. The real power stays the same. Find the total reactive power QC the capacitor bank must supply, in kvar.
A balanced three-phase load takes 60 kW at a power factor of 0.72 lagging from a 480 V (line-to-line), 60 Hz supply. A three-phase capacitor bank in parallel with the load must raise the overall power factor to 0.95 lagging. The real power stays the same. Find the total reactive power QC the capacitor bank must supply, in kvar.
Answer key
- 1. Iph = 24 A
- 2. IL = 13.86 A
- 3. P = 11.36 kW
- 4. P = 6.613 kW
- 5. QC = 169.7 kvar
- 6. QC = 38.11 kvar
Full step-by-step solutions: practise this topic on examproblems.com.