A balanced Y-connected load has an impedance of 9 + j12 Ω per phase. It is supplied from a balanced three-phase source with a line-to-line voltage of 600 V. Find the magnitude of the line current IL.
Three-phase power worksheet with answers
A balanced Δ-connected load has an impedance of 18 + j24 Ω per phase. It is supplied from a balanced three-phase source with a line-to-line voltage of 415 V. Find the magnitude of the line current IL.
A balanced Δ-connected load with an impedance of 3 + j4 Ω per phase is connected to a balanced three-phase supply with a line-to-line voltage of 415 V. Find the total real power P absorbed by the load in kW.
A balanced three-phase load draws a line current of 50 A from a supply with a line-to-line voltage of 480 V. The power factor is 0.9 lagging. Find the total real power P drawn by the load in kW.
A balanced three-phase load takes 100 kW at a power factor of 0.78 lagging from a 690 V (line-to-line), 50 Hz supply. A three-phase capacitor bank in parallel with the load must raise the overall power factor to 0.92 lagging. The real power stays the same. Find the total reactive power QC the capacitor bank must supply, in kvar.
A balanced three-phase load takes 200 kW at a power factor of 0.78 lagging from a 415 V (line-to-line), 50 Hz supply. A three-phase capacitor bank in parallel with the load must raise the overall power factor to 0.92 lagging. The real power stays the same. The capacitors are connected in Y. Find the capacitance Cph of each capacitor in µF.
Answer key
- 1. IL = 23.09 A
- 2. IL = 23.96 A
- 3. P = 62 kW
- 4. P = 37.41 kW
- 5. QC = 37.63 kvar
- 6. Cph = 1391 µF