Three-phase power worksheet with answers

Free printable Three-phase power worksheet: 6 problems from easy to exam level, with an answer key. Print it or save it as a PDF.

For teachers: free to print, copy and use in class. Every new worksheet has new values and its own answer key. A link to ExamProblems on your course page is appreciated.

Name: ____________________   Date: ____________

1.Easy
ABCVL​ = 415 VZ = 12 + j5 Ωper phase

A balanced Δ-connected load has an impedance of 12 + j5 Ω per phase. It is supplied from a balanced three-phase source with a line-to-line voltage of 415 V. Find the magnitude of the phase current Iph flowing through each impedance.

VL = 415 VZ = 12 + j5 Ω per phase
Iph = A
2.Easy
ABCVL​ = 400 VIL​ = ?Z = 24 + j7 Ωper phase

A balanced Δ-connected load has an impedance of 24 + j7 Ω per phase. It is supplied from a balanced three-phase source with a line-to-line voltage of 400 V. Find the magnitude of the line current IL.

VL = 400 VZ = 24 + j7 Ω per phase
IL = A
3.Medium
ABCVL​ = 480 VNZ = 15 + j20 Ωper phase

A balanced Y-connected load with an impedance of 15 + j20 Ω per phase is connected to a balanced three-phase supply with a line-to-line voltage of 480 V. Find the total real power P absorbed by the load in kW.

VL = 480 VZ = 15 + j20 Ω per phase
P = kW
4.Medium
ABCVL​ = 415 VIL​ = ?M11 kW, η = 90%cos φ = 0.84

A three-phase induction motor delivers 11 kW of mechanical output power at full load. At this load its efficiency is 90% and its power factor is 0.84 lagging. The supply has a line-to-line voltage of 415 V. Find the line current IL.

Pout = 11 kWη = 90%cos φ = 0.84VL = 415 V
IL = A
5.Hard
P = 300 kWφ1​S1​Q2​QC​

A balanced three-phase load takes 300 kW at a power factor of 0.72 lagging from a 415 V (line-to-line), 60 Hz supply. A three-phase capacitor bank in parallel with the load must raise the overall power factor to 0.9 lagging. The real power stays the same. The capacitors are connected in Y. Find the capacitance Cph of each capacitor in µF.

P = 300 kWpf1 = 0.72pf2 = 0.9VL = 415 Vf = 60 Hz
Cph = µF
6.Hard
P = 50 kWφ1​S1​Q2​QC​

A balanced three-phase load takes 50 kW at a power factor of 0.72 lagging from a 690 V (line-to-line), 60 Hz supply. A three-phase capacitor bank in parallel with the load must raise the overall power factor to 0.92 lagging. The real power stays the same. The capacitors are connected in Δ. Find the capacitance Cph of each capacitor in µF.

P = 50 kWpf1 = 0.72pf2 = 0.92VL = 690 Vf = 60 Hz
Cph = µF

Answer key

  1. 1. Iph = 31.92 A
  2. 2. IL = 27.71 A
  3. 3. P = 5.53 kW
  4. 4. IL = 20.24 A
  5. 5. Cph = 2216 µF
  6. 6. Cph = 49.94 µF

Full step-by-step solutions: practise this topic on examproblems.com.