Transformers worksheet with answers

Free printable Transformers worksheet: 6 problems from easy to exam level, with an answer key. Print it or save it as a PDF.

For teachers: free to print, copy and use in class. Every new worksheet has new values and its own answer key. A link to ExamProblems on your course page is appreciated.

Name: ____________________   Date: ____________

1.Easy
N1​ = 2400N2​ = 604800 VV2​ = ?

An ideal transformer has 2400 turns on its primary winding and 60 turns on its secondary winding. The primary is connected to a 4800 V AC supply. Find the secondary voltage V2.

N1 = 2400N2 = 60V1 = 4800 V
V2 = V
2.Easy
N1​ = 800N2​ = ?960 V120 V

An ideal transformer must step 960 V down to 120 V. Its primary winding has 800 turns. How many turns N2 does the secondary winding need?

V1 = 960 VV2 = 120 VN1 = 800
N2 =
3.Medium
6600 V230 VIHV​ = ?ILV​25 kVA

A single-phase 25 kVA, 6600/230 V transformer operates at its rated load. Treat it as ideal. Find the current IHV in the high-voltage winding.

S = 25 kVAV1 = 6600 VV2 = 230 V
IHV = A
4.Medium
RL​ = 24 Ω1011200 VV2​I1​ = ?I2​

An ideal transformer with a turns ratio N₁:N₂ = 10:1 has 1200 V applied to its primary winding. A 24 Ω resistor is connected across the secondary winding. Find the primary current I1.

N1:N2 = 10:1V1 = 1200 VRL = 24 Ω
I1 = A
5.Hard
150 kVA

A single-phase 150 kVA transformer has a core loss of 900 W and a copper loss of 1800 W at rated load. At what load Sη,max, in kVA, is its efficiency highest?

S = 150 kVAPcore = 900 WPcu,fl = 1800 W
Sη,max = kVA
6.Hard
pf 0.9250 kVA, η = 96%

A single-phase 250 kVA transformer has a core loss of 2000 W. At rated load and a power factor of 0.9 lagging its efficiency is 96%. Find the full-load copper loss Pcu,fl in watts.

S = 250 kVAPcore = 2000 Wpf = 0.9η = 96%
Pcu,fl = W

Answer key

  1. 1. V2 = 120 V
  2. 2. N2 = 100
  3. 3. IHV = 3.788 A
  4. 4. I1 = 0.5 A
  5. 5. Sη,max = 106.1 kVA
  6. 6. Pcu,fl = 7375 W

Full step-by-step solutions: practise this topic on examproblems.com.