An ideal transformer has 2000 turns on its primary winding and 50 turns on its secondary winding. The primary is connected to a 9600 V AC supply. Find the secondary voltage V2.
Transformers worksheet with answers
An ideal transformer has 60 turns on its primary winding and 600 turns on its secondary winding. The primary is connected to a 240 V AC supply. Find the secondary voltage V2.
A single-phase 100 kVA, 6600/230 V transformer operates at its rated load. Treat it as ideal. Find the current ILV in the low-voltage winding.
A single-phase 25 kVA, 4800/240 V transformer operates at its rated load. Treat it as ideal. Find the current IHV in the high-voltage winding.
A single-phase 500 kVA transformer has a core loss of 2500 W and a copper loss of 3750 W at rated load. It supplies 25% of its rated kVA at a power factor of 0.9 lagging. Find the total losses Ploss in watts at this load.
A single-phase 500 kVA transformer has a core loss of 2000 W and a copper loss of 3000 W at rated load. At what load Sη,max, in kVA, is its efficiency highest?
Answer key
- 1. V2 = 240 V
- 2. V2 = 2400 V
- 3. ILV = 434.8 A
- 4. IHV = 5.208 A
- 5. Ploss = 2734 W
- 6. Sη,max = 408.2 kVA