An ideal transformer has 100 turns on its primary winding and 2500 turns on its secondary winding. The primary is connected to a 230 V AC supply. Find the secondary voltage V2.
Transformers worksheet with answers
An ideal transformer must step 920 V down to 230 V. Its primary winding has 80 turns. How many turns N2 does the secondary winding need?
A single-phase 100 kVA, 11000/400 V transformer operates at its rated load. Treat it as ideal. Find the current ILV in the low-voltage winding.
An ideal transformer with a turns ratio N₁:N₂ = 2:1 has 240 V applied to its primary winding. An 8 Ω resistor is connected across the secondary winding. Find the primary current I1.
A single-phase 75 kVA transformer has a core loss of 300 W and a copper loss of 600 W at rated load. It supplies 25% of its rated kVA at a power factor of 0.9 lagging. Find the total losses Ploss in watts at this load.
A single-phase 150 kVA transformer has a core loss of 750 W and a copper loss of 2250 W at rated load. At what load Sη,max, in kVA, is its efficiency highest?
Answer key
- 1. V2 = 5750 V
- 2. N2 = 20
- 3. ILV = 250 A
- 4. I1 = 7.5 A
- 5. Ploss = 337.5 W
- 6. Sη,max = 86.6 kVA