An ideal transformer has 100 turns on its primary winding and 20 turns on its secondary winding. The primary is connected to a 2000 V AC supply. Find the secondary voltage V2.
Transformers worksheet with answers
An ideal transformer has 3000 turns on its primary winding and 120 turns on its secondary winding. The primary is connected to a 5750 V AC supply. Find the secondary voltage V2.
A 5 Ω resistor is connected across the secondary winding of an ideal transformer with a turns ratio N₁:N₂ = 12:1. Find the resistance R1′ seen looking into the primary winding.
An ideal transformer with a turns ratio N₁:N₂ = 2:1 has 460 V applied to its primary winding. A 48 Ω resistor is connected across the secondary winding. Find the primary current I1.
A single-phase 75 kVA transformer has a core loss of 450 W and a copper loss of 1800 W at rated load. At what load Sη,max, in kVA, is its efficiency highest?
A single-phase 100 kVA transformer has a core loss of 600 W and a copper loss of 1800 W at rated load. It supplies 75% of its rated kVA at a power factor of 0.9 lagging. Find the total losses Ploss in watts at this load.
Answer key
- 1. V2 = 400 V
- 2. V2 = 230 V
- 3. R1′ = 720 Ω
- 4. I1 = 2.396 A
- 5. Sη,max = 37.5 kVA
- 6. Ploss = 1613 W