An ideal transformer has 120 turns on its primary winding and 960 turns on its secondary winding. The primary is connected to a 110 V AC supply. Find the secondary voltage V2.
Transformers worksheet with answers
An ideal transformer has 400 turns on its primary winding and 80 turns on its secondary winding. The primary is connected to a 2000 V AC supply. Find the secondary voltage V2.
A single-phase 10 kVA, 2400/240 V transformer operates at its rated load. Treat it as ideal. Find the current IHV in the high-voltage winding.
A 16 Ω resistor is connected across the secondary winding of an ideal transformer with a turns ratio N₁:N₂ = 10:1. Find the resistance R1′ seen looking into the primary winding.
A single-phase 50 kVA transformer has a core loss of 400 W. At rated load and a power factor of 0.8 lagging its efficiency is 98%. Find the full-load copper loss Pcu,fl in watts.
A single-phase 25 kVA transformer has a core loss of 125 W and a copper loss of 375 W at rated load. At what load Sη,max, in kVA, is its efficiency highest?
Answer key
- 1. V2 = 880 V
- 2. V2 = 400 V
- 3. IHV = 4.167 A
- 4. R1′ = 1600 Ω
- 5. Pcu,fl = 416.3 W
- 6. Sη,max = 14.43 kVA