An ideal transformer must step 960 V down to 120 V. Its primary winding has 800 turns. How many turns N2 does the secondary winding need?
Transformers worksheet with answers
An ideal transformer must step 480 V down to 240 V. Its primary winding has 80 turns. How many turns N2 does the secondary winding need?
A single-phase 25 kVA, 6600/230 V transformer operates at its rated load. Treat it as ideal. Find the current IHV in the high-voltage winding.
A single-phase 250 kVA, 480/240 V transformer operates at its rated load. Treat it as ideal. Find the current ILV in the low-voltage winding.
A single-phase 150 kVA transformer has a core loss of 1200 W and a copper loss of 1800 W at rated load. It supplies 50% of its rated kVA at a power factor of 0.8 lagging. Find the total losses Ploss in watts at this load.
A single-phase 250 kVA transformer has a core loss of 1250 W and a copper loss of 5000 W at rated load. It supplies 50% of its rated kVA at a power factor of 0.9 lagging. Find the total losses Ploss in watts at this load.
Answer key
- 1. N2 = 100
- 2. N2 = 40
- 3. IHV = 3.788 A
- 4. ILV = 1042 A
- 5. Ploss = 1650 W
- 6. Ploss = 2500 W