An ideal transformer has 150 turns on its primary winding and 7500 turns on its secondary winding. The primary is connected to a 110 V AC supply. Find the secondary voltage V2.
Transformers worksheet with answers
An ideal transformer has 240 turns on its primary winding and 60 turns on its secondary winding. The primary is connected to a 920 V AC supply. Find the secondary voltage V2.
An ideal transformer with a turns ratio N₁:N₂ = 4:1 has 480 V applied to its primary winding. A 12 Ω resistor is connected across the secondary winding. Find the primary current I1.
An ideal transformer with a turns ratio N₁:N₂ = 2:1 has 460 V applied to its primary winding. A 6 Ω resistor is connected across the secondary winding. Find the primary current I1.
A single-phase 50 kVA transformer has a core loss of 250 W and a copper loss of 750 W at rated load. It supplies 25% of its rated kVA at a power factor of 0.95 lagging. Find the total losses Ploss in watts at this load.
A single-phase 25 kVA transformer has a core loss of 100 W. At rated load and a power factor of 0.95 lagging its efficiency is 99%. Find the full-load copper loss Pcu,fl in watts.
Answer key
- 1. V2 = 5500 V
- 2. V2 = 230 V
- 3. I1 = 2.5 A
- 4. I1 = 19.17 A
- 5. Ploss = 296.9 W
- 6. Pcu,fl = 139.9 W