An ideal transformer must step 960 V down to 120 V. Its primary winding has 160 turns. How many turns N2 does the secondary winding need?
Transformers worksheet with answers
An ideal transformer has 80 turns on its primary winding and 320 turns on its secondary winding. The primary is connected to a 230 V AC supply. Find the secondary voltage V2.
An ideal transformer with a turns ratio N₁:N₂ = 10:1 has 1200 V applied to its primary winding. A 4 Ω resistor is connected across the secondary winding. Find the primary current I1.
A single-phase 250 kVA, 4800/240 V transformer operates at its rated load. Treat it as ideal. Find the current ILV in the low-voltage winding.
A single-phase 75 kVA transformer has a core loss of 225 W and a copper loss of 562.5 W at rated load. It supplies 25% of its rated kVA at a power factor of 0.85 lagging. Find the total losses Ploss in watts at this load.
A single-phase 500 kVA transformer has a core loss of 1500 W. At rated load and a power factor of 0.85 lagging its efficiency is 98.8%. Find the full-load copper loss Pcu,fl in watts.
Answer key
- 1. N2 = 20
- 2. V2 = 920 V
- 3. I1 = 3 A
- 4. ILV = 1042 A
- 5. Ploss = 260.2 W
- 6. Pcu,fl = 3662 W