An ideal transformer must step 9200 V down to 230 V. Its primary winding has 2000 turns. How many turns N2 does the secondary winding need?
Transformers worksheet with answers
An ideal transformer must step 3840 V down to 240 V. Its primary winding has 800 turns. How many turns N2 does the secondary winding need?
An ideal transformer with a turns ratio N₁:N₂ = 10:1 has 2300 V applied to its primary winding. An 8 Ω resistor is connected across the secondary winding. Find the primary current I1.
An ideal transformer with a turns ratio N₁:N₂ = 2:1 has 240 V applied to its primary winding. An 8 Ω resistor is connected across the secondary winding. Find the primary current I1.
A single-phase 200 kVA transformer has a core loss of 1600 W and a copper loss of 4800 W at rated load. At what load Sη,max, in kVA, is its efficiency highest?
A single-phase 200 kVA transformer has a core loss of 800 W. At rated load and a power factor of 0.8 lagging its efficiency is 98.8%. Find the full-load copper loss Pcu,fl in watts.
Answer key
- 1. N2 = 50
- 2. N2 = 50
- 3. I1 = 2.875 A
- 4. I1 = 7.5 A
- 5. Sη,max = 115.5 kVA
- 6. Pcu,fl = 1143 W