An ideal transformer must step 3840 V down to 240 V. Its primary winding has 1920 turns. How many turns N2 does the secondary winding need?
Transformers worksheet with answers
An ideal transformer must step 960 V down to 240 V. Its primary winding has 600 turns. How many turns N2 does the secondary winding need?
An ideal transformer with a turns ratio N₁:N₂ = 4:1 has 480 V applied to its primary winding. A 4 Ω resistor is connected across the secondary winding. Find the primary current I1.
An ideal transformer with a turns ratio N₁:N₂ = 2:1 has 460 V applied to its primary winding. A 20 Ω resistor is connected across the secondary winding. Find the primary current I1.
A single-phase 200 kVA transformer has a core loss of 1600 W and a copper loss of 3200 W at rated load. At what load Sη,max, in kVA, is its efficiency highest?
A single-phase 75 kVA transformer has a core loss of 450 W and a copper loss of 1125 W at rated load. It supplies 50% of its rated kVA at a power factor of 0.95 lagging. Find the total losses Ploss in watts at this load.
Answer key
- 1. N2 = 120
- 2. N2 = 150
- 3. I1 = 7.5 A
- 4. I1 = 5.75 A
- 5. Sη,max = 141.4 kVA
- 6. Ploss = 731.3 W