An ideal transformer must step 480 V down to 120 V. Its primary winding has 200 turns. How many turns N2 does the secondary winding need?
Transformers worksheet with answers
An ideal transformer has 120 turns on its primary winding and 3000 turns on its secondary winding. The primary is connected to a 230 V AC supply. Find the secondary voltage V2.
A 16 Ω resistor is connected across the secondary winding of an ideal transformer with a turns ratio N₁:N₂ = 2:1. Find the resistance R1′ seen looking into the primary winding.
A single-phase 75 kVA, 6600/230 V transformer operates at its rated load. Treat it as ideal. Find the current ILV in the low-voltage winding.
A single-phase 100 kVA transformer has a core loss of 800 W and a copper loss of 3200 W at rated load. It supplies 75% of its rated kVA at a power factor of 0.8 lagging. Find the total losses Ploss in watts at this load.
A single-phase 75 kVA transformer has a core loss of 450 W and a copper loss of 1125 W at rated load. It supplies 50% of its rated kVA at a power factor of 0.9 lagging. Find the total losses Ploss in watts at this load.
Answer key
- 1. N2 = 50
- 2. V2 = 5750 V
- 3. R1′ = 64 Ω
- 4. ILV = 326.1 A
- 5. Ploss = 2600 W
- 6. Ploss = 731.3 W