An ideal transformer must step 600 V down to 120 V. Its primary winding has 500 turns. How many turns N2 does the secondary winding need?
Transformers worksheet with answers
An ideal transformer has 3000 turns on its primary winding and 120 turns on its secondary winding. The primary is connected to a 10000 V AC supply. Find the secondary voltage V2.
A single-phase 100 kVA, 7200/240 V transformer operates at its rated load. Treat it as ideal. Find the current ILV in the low-voltage winding.
A 5 Ω resistor is connected across the secondary winding of an ideal transformer with a turns ratio N₁:N₂ = 4:1. Find the resistance R1′ seen looking into the primary winding.
A single-phase 50 kVA transformer has a core loss of 400 W and a copper loss of 1600 W at rated load. At what load Sη,max, in kVA, is its efficiency highest?
A single-phase 500 kVA transformer has a core loss of 4000 W. At rated load and a power factor of 0.9 lagging its efficiency is 96.5%. Find the full-load copper loss Pcu,fl in watts.
Answer key
- 1. N2 = 100
- 2. V2 = 400 V
- 3. ILV = 416.7 A
- 4. R1′ = 80 Ω
- 5. Sη,max = 25 kVA
- 6. Pcu,fl = 12321 W