An ideal transformer must step 3840 V down to 240 V. Its primary winding has 3200 turns. How many turns N2 does the secondary winding need?
Transformers worksheet with answers
An ideal transformer has 120 turns on its primary winding and 2400 turns on its secondary winding. The primary is connected to a 690 V AC supply. Find the secondary voltage V2.
An amplifier with an output resistance of 800 Ω drives a 50 Ω loudspeaker through an ideal transformer. For maximum power transfer the loudspeaker must look like 800 Ω from the amplifier. Find the turns ratio a = N₁/N₂.
A single-phase 500 kVA, 4160/480 V transformer operates at its rated load. Treat it as ideal. Find the current ILV in the low-voltage winding.
A single-phase 500 kVA transformer has a core loss of 2500 W. At rated load and a power factor of 0.9 lagging its efficiency is 98%. Find the full-load copper loss Pcu,fl in watts.
A single-phase 50 kVA transformer has a core loss of 200 W and a copper loss of 600 W at rated load. It supplies 25% of its rated kVA at a power factor of 0.85 lagging. Find the total losses Ploss in watts at this load.
Answer key
- 1. N2 = 200
- 2. V2 = 13800 V
- 3. a = 4
- 4. ILV = 1042 A
- 5. Pcu,fl = 6684 W
- 6. Ploss = 237.5 W
Full step-by-step solutions: practise this topic on examproblems.com.