An ideal transformer must step 1200 V down to 240 V. Its primary winding has 500 turns. How many turns N2 does the secondary winding need?
Transformers worksheet with answers
An ideal transformer has 250 turns on its primary winding and 25 turns on its secondary winding. The primary is connected to a 2300 V AC supply. Find the secondary voltage V2.
A 10 Ω resistor is connected across the secondary winding of an ideal transformer with a turns ratio N₁:N₂ = 8:1. Find the resistance R1′ seen looking into the primary winding.
A single-phase 25 kVA, 4160/480 V transformer operates at its rated load. Treat it as ideal. Find the current ILV in the low-voltage winding.
A single-phase 50 kVA transformer has a core loss of 150 W and a copper loss of 375 W at rated load. It supplies 75% of its rated kVA at a power factor of 0.95 lagging. Find the total losses Ploss in watts at this load.
A single-phase 50 kVA transformer has a core loss of 300 W and a copper loss of 750 W at rated load. It supplies 25% of its rated kVA at a power factor of 0.8 lagging. Find the total losses Ploss in watts at this load.
Answer key
- 1. N2 = 100
- 2. V2 = 230 V
- 3. R1′ = 640 Ω
- 4. ILV = 52.08 A
- 5. Ploss = 360.9 W
- 6. Ploss = 346.9 W