An ideal transformer has 7500 turns on its primary winding and 150 turns on its secondary winding. The primary is connected to a 6000 V AC supply. Find the secondary voltage V2.
Transformers worksheet with answers
An ideal transformer has 1600 turns on its primary winding and 200 turns on its secondary winding. The primary is connected to a 960 V AC supply. Find the secondary voltage V2.
A 5 Ω resistor is connected across the secondary winding of an ideal transformer with a turns ratio N₁:N₂ = 8:1. Find the resistance R1′ seen looking into the primary winding.
A single-phase 500 kVA, 6600/230 V transformer operates at its rated load. Treat it as ideal. Find the current ILV in the low-voltage winding.
A single-phase 75 kVA transformer has a core loss of 300 W and a copper loss of 900 W at rated load. At what load Sη,max, in kVA, is its efficiency highest?
A single-phase 50 kVA transformer has a core loss of 150 W and a copper loss of 600 W at rated load. It supplies 75% of its rated kVA at a power factor of 0.8 lagging. Find the total losses Ploss in watts at this load.
Answer key
- 1. V2 = 120 V
- 2. V2 = 120 V
- 3. R1′ = 320 Ω
- 4. ILV = 2174 A
- 5. Sη,max = 43.3 kVA
- 6. Ploss = 487.5 W
Full step-by-step solutions: practise this topic on examproblems.com.