An ideal transformer must step 960 V down to 240 V. Its primary winding has 200 turns. How many turns N2 does the secondary winding need?
Transformers worksheet with answers
An ideal transformer must step 2400 V down to 240 V. Its primary winding has 200 turns. How many turns N2 does the secondary winding need?
A single-phase 10 kVA, 480/240 V transformer operates at its rated load. Treat it as ideal. Find the current IHV in the high-voltage winding.
An ideal transformer with a turns ratio N₁:N₂ = 2:1 has 480 V applied to its primary winding. A 30 Ω resistor is connected across the secondary winding. Find the primary current I1.
A single-phase 50 kVA transformer has a core loss of 400 W. At rated load and a power factor of 0.95 lagging its efficiency is 96%. Find the full-load copper loss Pcu,fl in watts.
A single-phase 500 kVA transformer has a core loss of 1500 W and a copper loss of 3750 W at rated load. At what load Sη,max, in kVA, is its efficiency highest?
Answer key
- 1. N2 = 50
- 2. N2 = 20
- 3. IHV = 20.83 A
- 4. I1 = 4 A
- 5. Pcu,fl = 1579 W
- 6. Sη,max = 316.2 kVA