The inductor carries no current before the switch closes at t = 0. Find the current i at t = 1 ms.
Vs = 6 VR = 50 ΩL = 22 mHt = 1 ms
i = A
8.RC & RL transientsHard
A timer starts charging an uncharged capacitor through a resistor from a 5 V supply at t = 0. It must trigger when the capacitor voltage reaches 4.5 V, exactly 200 ms after the start. With R = 47 kΩ, find the capacitance C needed.
Vs = 5 VVth = 4.5 VT = 200 msR = 47 kΩ
C = µF
9.AC impedance & phasorsMedium
A series RLC circuit is connected to a 230 V (rms), 50 Hz supply. Find the power factor cos φ of the circuit.
V = 230 V (rms)f = 50 HzR = 10 ΩL = 150 mHC = 47 µF
cos φ =
10.AC impedance & phasorsHard
A series RLC circuit is connected to a 12 V (rms), 50 Hz supply. Find the rms current I.
V = 12 V (rms)f = 50 HzR = 25 ΩL = 100 mHC = 47 µF
I = A
11.AC power & power factorMedium
A single-phase motor takes 33 kW at a power factor of 0.8 lagging from a 400 V supply. Find the reactive power Q it draws.
P = 33 kWpf = 0.8V = 400 V
Q = kvar
12.AC power & power factorHard
A 24 V (rms), 50 Hz source has an internal impedance Zs = 50 + j30 Ω. The load impedance ZL can be chosen freely. The load for maximum power is built from a resistor in series with a capacitor. Find the capacitance C.
Vs = 24 V (rms)f = 50 HzZs = 50 + j30 Ω
C = µF
13.Three-phase powerMedium
A three-phase induction motor delivers 110 kW of mechanical output power at full load. At this load its efficiency is 92% and its power factor is 0.85 lagging. The supply has a line-to-line voltage of 480 V. Find the line current IL.
Pout = 110 kWη = 92%cos φ = 0.85VL = 480 V
IL = A
14.Three-phase powerHard
A balanced three-phase load takes 300 kW at a power factor of 0.78 lagging from a 415 V (line-to-line), 50 Hz supply. A three-phase capacitor bank in parallel with the load must raise the overall power factor to 0.92 lagging. The real power stays the same. Find the total reactive power QC the capacitor bank must supply, in kvar.
P = 300 kWpf1 = 0.78pf2 = 0.92VL = 415 Vf = 50 Hz
QC = kvar
15.TransformersMedium
A single-phase 250 kVA, 480/240 V transformer operates at its rated load. Treat it as ideal. Find the current IHV in the high-voltage winding.
S = 250 kVAV1 = 480 VV2 = 240 V
IHV = A
16.TransformersHard
A single-phase 200 kVA transformer has a core loss of 1200 W. At rated load and a power factor of 0.9 lagging its efficiency is 96%. Find the full-load copper loss Pcu,fl in watts.
S = 200 kVAPcore = 1200 Wpf = 0.9η = 96%
Pcu,fl = W
3Solutions
1.Series & parallel resistors
Answer: Req = 24 Ω
Series and parallel resistors: in series the same current flows through each resistor and R = R₁ + R₂ + …. In parallel each resistor has the same voltage and 1/R = 1/R₁ + 1/R₂ + …. A ladder network is reduced one pair at a time until a single equivalent resistance remains.
Combine resistors from the far end
Start at the end farthest from the source and work back towards it. Resistors carrying the same current are in series; resistors across the same two nodes are in parallel.
R3 + R4 = 12 + 8 = 20 Ω
R2 ∥ 20 = 5·20/(5+20) = 4 Ω
Req = R1 + 4 = 20 + 4 = 24 Ω
Answer
Req = 24 Ω
2.Series & parallel resistors
Answer: Req = 22.2 Ω
Series and parallel resistors: in series the same current flows through each resistor and R = R₁ + R₂ + …. In parallel each resistor has the same voltage and 1/R = 1/R₁ + 1/R₂ + …. A ladder network is reduced one pair at a time until a single equivalent resistance remains.
Combine resistors from the far end
Start at the end farthest from the source and work back towards it. Resistors carrying the same current are in series; resistors across the same two nodes are in parallel.
R5 + R6 = 3 + 30 = 33 Ω
R4 ∥ 33 = 15.71 Ω
R3 + 15.71 = 25.71 Ω
R2 ∥ 25.71 = 7.2 Ω
Req = R1 + 7.2 = 15 + 7.2 = 22.2 Ω
Answer
Req = 22.2 Ω
3.Nodal analysis
Answer: VA = 5.696 V
Nodal analysis: choose a reference node, label the unknown node voltages, write Kirchhoff’s current law at each unknown node using Ohm’s law (I = ΔV/R), and solve the resulting equations.
Set up the nodes
Ground is the bottom wire. Known node voltages come straight from the sources (V1 = 9 V). Unknowns: VA, VB.
KCL at node A
Currents leaving A through the resistors equal the current pushed into A by sources.
VA/R2 + (VA − V1)/R1 + (VA − VB)/R3 = 0
VA/20 + (VA − 9)/3 + (VA − VB)/12 = 0
0.4667·VA − 0.08333·VB = 3
KCL at node B
Currents leaving B through the resistors equal the current pushed into B by sources.
Nodal analysis: choose a reference node, label the unknown node voltages, write Kirchhoff’s current law at each unknown node using Ohm’s law (I = ΔV/R), and solve the resulting equations.
Set up the nodes
Ground is the bottom wire. Known node voltages come straight from the sources (V1 = 5 V, V2 = −10 V). Unknowns: VA, VB.
KCL at node A
Currents leaving A through the resistors equal the current pushed into A by sources.
VA/R3 + (VA − V1)/R1 + (VA − VB)/R2 = 0
VA/30 + (VA − 5)/20 + (VA − VB)/3 = 0
0.4167·VA − 0.3333·VB = 0.25
KCL at node B
Currents leaving B through the resistors equal the current pushed into B by sources.
VB/R5 + (VB − VA)/R2 + (VB − V2)/R4 = Is
VB/2 + (VB − VA)/3 + (VB − (−10))/2 = 5
−0.3333·VA + 1.333·VB = 0
Solve
Δ = (0.4167)(1.333) − (−0.3333)(−0.3333) = 0.4444
VA = Δ1/Δ = 0.3333/0.4444 = 0.75 V
VB = Δ2/Δ = 0.08333/0.4444 = 0.1875 V
Answer
IR2 = (VA − VB)/R2 = (0.75 − 0.1875)/3 = 0.1875 A
5.Thévenin & Norton
Answer: IL = 0.2479 A
Thévenin’s theorem: any linear two-terminal network behaves like a single voltage source Vth in series with a resistance Rth. Norton’s theorem gives the same network as a current source IN = Vth/Rth in parallel with Rth.
Find Rth with every source switched off
Replace voltage sources with shorts and current sources with opens, then look into the circuit from a–b.
R1 ∥ R2 = 8·10/(8+10) = 4.444 Ω
Rth = (R1 ∥ R2) + R3 = 4.444 + 3 = 7.444 Ω
Find Vth, the open-circuit voltage
With a–b open, no current flows through R₃, so there is no drop across it and V_b = V_A. R₁ and R₂ form a voltage divider.
Vth = V1·R2/(R1+R2) = 6·10/(8+10) = 3.333 V
Connect the load to the Thévenin equivalent
The Thévenin source and R_th in series behave exactly like the original circuit at a–b, so the load sees a simple series loop.
IL = Vth/(Rth + RL) = 3.333/(7.444 + 6) = 0.2479 A
6.Thévenin & Norton
Answer: IL = 1.756 A
Thévenin’s theorem: any linear two-terminal network behaves like a single voltage source Vth in series with a resistance Rth. Norton’s theorem gives the same network as a current source IN = Vth/Rth in parallel with Rth.
Find Rth with every source switched off
Replace voltage sources with shorts and current sources with opens, then look into the circuit from a–b.
R1 ∥ R2 = 15·3/(15+3) = 2.5 Ω
Rth = (R1 ∥ R2) + R3 = 2.5 + 5 = 7.5 Ω
Find Vth, the open-circuit voltage
With a–b open, the only path for Iₛ is through R₃ into node A. Find V_A by superposition of V₁ and Iₛ, then add the drop across R₃.
VA = V1·R2/(R1+R2) + Is·(R1∥R2) = 2 + 5·2.5 = 14.5 V
Vth = VB = VA + Is·R3 = 14.5 + 5·5 = 39.5 V
Connect the load to the Thévenin equivalent
The Thévenin source and R_th in series behave exactly like the original circuit at a–b, so the load sees a simple series loop.
IL = Vth/(Rth + RL) = 39.5/(7.5 + 15) = 1.756 A
7.RC & RL transients
Answer: i = 0.1076 A
First-order transients: in a circuit with one capacitor or one inductor, every voltage and current moves exponentially from its initial value to its final value: x(t) = x(∞) + [x(0) − x(∞)]·e−t/τ, with τ = RC or τ = L/R. After about 5τ the circuit has settled.
Time constant and final current
Long after the switch closes the inductor behaves like a short circuit, so the final current is set by R alone.
First-order transients: in a circuit with one capacitor or one inductor, every voltage and current moves exponentially from its initial value to its final value: x(t) = x(∞) + [x(0) − x(∞)]·e−t/τ, with τ = RC or τ = L/R. After about 5τ the circuit has settled.
Required time constant
4.5 = 5·(1 − e−200/τ) → τ = 200/ln(5/(5 − 4.5))
τ = 200/2.303 = 86.86 ms
Capacitance
kΩ times µF gives milliseconds.
C = τ/R = 86.86/47 = 1.848 µF
Answer
C = 1.848 µF
9.AC impedance & phasors
Answer: cos φ = 0.4367
AC circuits with phasors: resistors, inductors and capacitors have impedances R, jωL and 1/(jωC), with ω = 2πf. In series, impedances add like resistances, but as complex numbers. Rms current and voltage follow Ohm’s law with |Z|.
Reactances
XL = 47.12 Ω, XC = 67.73 Ω
Impedance
|Z| = √(10² + (−20.6)²) = 22.9 Ω
Power factor
cos φ = R/|Z| = 10/22.9 = 0.4367
The circuit is capacitive, so the power factor is leading.
Answer
cos φ = 0.4367
10.AC impedance & phasors
Answer: I = 0.2722 A
AC circuits with phasors: resistors, inductors and capacitors have impedances R, jωL and 1/(jωC), with ω = 2πf. In series, impedances add like resistances, but as complex numbers. Rms current and voltage follow Ohm’s law with |Z|.
Reactances
ω = 2πf = 2π·50 = 314.2 rad/s
XL = ωL = 314.2·0.1 = 31.42 Ω
XC = 1/(ωC) = 1/(314.2·47·10⁻⁶) = 67.73 Ω
Impedance
In series the impedances add as complex numbers: Z = R + j(XL − XC).
The same current flows through every element of a series circuit.
I = V/|Z| = 12/44.08 = 0.2722 A
Answer
I = 0.2722 A
11.AC power & power factor
Answer: Q = 24.75 kvar
AC power: apparent power S = V·I (VA) splits into real power P = S·cos φ (W), which does useful work, and reactive power Q = S·sin φ (var), which moves back and forth between source and load. The power factor is cos φ. A capacitor in parallel supplies reactive power locally, so the line current drops for the same real power.
Angle
φ = arccos(0.8) = 36.87°, tan φ = 0.75
Reactive power
Q = P·tan φ = 33·0.75 = 24.75 kvar
Answer
Q = 24.75 kvar
12.AC power & power factor
Answer: C = 106.1 µF
AC power: apparent power S = V·I (VA) splits into real power P = S·cos φ (W), which does useful work, and reactive power Q = S·sin φ (var), which moves back and forth between source and load. The power factor is cos φ. A capacitor in parallel supplies reactive power locally, so the line current drops for the same real power.
Conjugate match
The load reactance cancels the source reactance, and the load resistance equals the source resistance.
ZL = Zs* = 50 − j30 Ω
Capacitance
XC = 30 Ω → C = 1/(2π·50·30) = 106.1 µF
Answer
C = 106.1 µF
13.Three-phase power
Answer: IL = 169.2 A
Balanced three-phase systems: in a Y (star) connection the line-to-line voltage is √3 times the phase voltage, VL = √3·Vph, and the line current equals the phase current. In a Δ (delta) connection the line-to-line voltage equals the phase voltage and the line current is √3 times the phase current, IL = √3·Iph. The total power is three times the power of one phase: P = 3·Vph·Iph·cos φ = √3·VL·IL·cos φ.
Electrical input power
Pin = Pout/η = 110/0.92 = 119.6 kW
Line current
IL = Pin/(√3·VL·cos φ) = 119565/(√3·480·0.85) = 169.2 A
Answer
IL = 169.2 A
14.Three-phase power
Answer: QC = 112.9 kvar
Balanced three-phase systems: in a Y (star) connection the line-to-line voltage is √3 times the phase voltage, VL = √3·Vph, and the line current equals the phase current. In a Δ (delta) connection the line-to-line voltage equals the phase voltage and the line current is √3 times the phase current, IL = √3·Iph. The total power is three times the power of one phase: P = 3·Vph·Iph·cos φ = √3·VL·IL·cos φ. Power factor correction: capacitors supply reactive power locally, QC = P·(tan φ1 − tan φ2). Each of the three capacitors supplies QC/3 = V²·ω·C, where V is the voltage across that capacitor: VL in a Δ bank, VL/√3 in a Y bank.
Reactive power before and after
The real power is unchanged, so each power factor fixes the reactive power: Q = P·tan φ.
Q1 = 300·tan(acos 0.78) = 300·0.8023 = 240.7 kvar
Q2 = 300·tan(acos 0.92) = 300·0.426 = 127.8 kvar
Reactive power from the capacitors
QC = Q1 − Q2 = 112.9 kvar
Answer
QC = 112.9 kvar
15.Transformers
Answer: IHV = 520.8 A
Ideal transformer: the voltages are in the ratio of the turns and the currents in the inverse ratio: V₁/V₂ = N₁/N₂ = a and I₁/I₂ = N₂/N₁ = 1/a, so the power in equals the power out, V₁·I₁ = V₂·I₂. A load impedance Z on the secondary looks like a²·Z from the primary.
Rated current
Both windings carry the same apparent power.
IHV = S/V = 250000/480 = 520.8 A
Answer
IHV = 520.8 A
16.Transformers
Answer: Pcu,fl = 6300 W
Transformer losses: the core loss (hysteresis and eddy currents) depends on the voltage and is the same at any load. The copper loss in the windings goes with the current squared, so at a fraction x of rated load it is x²·Pcu,fl. Efficiency η = Pout/(Pout + Pcore + Pcu), with Pout = x·S·pf. The efficiency is highest at the load where the copper loss equals the core loss.