Heat conduction
- Fourier’s law
- Q̇ = kAΔT/L
- Conduction resistance
- R = L/(kA)
- Convection resistance
- R = 1/(hA)
- Resistances in series
- Q̇ = ΔTtotal/ΣR
- U-value
- U = 1/(ΣR·A)
Formula sheets, the key method steps for every topic and 4 practice problems, with full solutions at the back.
A wall is made of 50 mm of brick and 50 mm of glass, with an area of 15 m². The outer faces are at 20 °C and -1 °C. Find the temperature Ti at the interface between the two layers.
A wall of 100 mm gypsum board and 100 mm mineral wool separates a room at 20 °C from outside air at -6 °C. The convection coefficients are 7.7 W/(m²·K) inside and 25 W/(m²·K) outside, and the wall area is 4 m². Find the temperature Ts of the inside surface of the wall.
In a condenser, steam condenses at a constant 110 °C on the outside of the tubes. Cooling water (0.5 kg/s, cp = 4.18 kJ/(kg·K)) flows through the tubes and heats from 20 to 90 °C. The overall heat transfer coefficient is 2000 W/(m²·K). Find the heat transfer area A needed.
Steam condenses at a constant 130 °C on the outside of the tubes of a condenser with a heat transfer area of 2 m² and U = 1500 W/(m²·K). Cooling water (0.5 kg/s, cp = 4.18 kJ/(kg·K)) enters the tubes at 10 °C. Find the water outlet temperature Tc,out.
Answer: Ti = 8 °C
Thermal resistance: steady heat flow through layers in series behaves like current through resistors in series: Q̇ = ΔT/ΣR, with R = L/(kA) for a conducting layer and R = 1/(hA) for a convecting surface. The temperature drop across each layer is proportional to its resistance.
The temperature drops across the first layer by Q̇·R₁.
Answer: Ts = 18.96 °C
Thermal resistance: steady heat flow through layers in series behaves like current through resistors in series: Q̇ = ΔT/ΣR, with R = L/(kA) for a conducting layer and R = 1/(hA) for a convecting surface. The temperature drop across each layer is proportional to its resistance.
Answer: A = 1.572 m²
LMTD method: the temperature difference between the streams changes along the exchanger, so the rate equation uses its logarithmic mean: Q̇ = U·A·ΔTlm, with ΔTlm = (ΔT₁ − ΔT₂)/ln(ΔT₁/ΔT₂), where ΔT₁ and ΔT₂ are the differences at the two ends. Counter-flow gives a larger ΔTlm than parallel flow for the same inlet and outlet temperatures.
Answer: Tc,out = 101.4 °C
LMTD method: the temperature difference between the streams changes along the exchanger, so the rate equation uses its logarithmic mean: Q̇ = U·A·ΔTlm, with ΔTlm = (ΔT₁ − ΔT₂)/ln(ΔT₁/ΔT₂), where ΔT₁ and ΔT₂ are the differences at the two ends. Counter-flow gives a larger ΔTlm than parallel flow for the same inlet and outlet temperatures.
With ΔT₁ = Ts − Tc,in and ΔT₂ = Ts − Tc,out, the difference ΔT₁ − ΔT₂ equals the water temperature rise, so the rise cancels.
Heat transferred: Q̇ = 191.1 kW.