Heat conduction
- Fourier’s law
- Q̇ = kAΔT/L
- Conduction resistance
- R = L/(kA)
- Convection resistance
- R = 1/(hA)
- Resistances in series
- Q̇ = ΔTtotal/ΣR
- U-value
- U = 1/(ΣR·A)
Formula sheets, the key method steps for every topic and 4 practice problems, with full solutions at the back.
A wall is made of 200 mm of mineral wool and 100 mm of gypsum board, with an area of 20 m². The outer faces are at 17 °C and -4 °C. Find the temperature Ti at the interface between the two layers.
A wall of 50 mm expanded polystyrene and 100 mm glass separates a room at 21 °C from outside air at 1 °C. The convection coefficients are 7.7 W/(m²·K) inside and 20 W/(m²·K) outside, and the wall area is 4 m². Find the overall heat transfer coefficient U of the wall.
A counter-flow heat exchanger transfers 420 kW. The hot fluid cools from 180 to 60 °C and the cold fluid heats from 25 to 160 °C. The overall heat transfer coefficient is 300 W/(m²·K). Find the heat transfer area A needed.
Hot oil (1.5 kg/s, cp = 2.3 kJ/(kg·K)) cools from 90 to 65 °C in a counter-flow exchanger. It heats 1.5 kg/s of water (cp = 4.18 kJ/(kg·K)) that enters at 20 °C. With U = 500 W/(m²·K), find the heat transfer area A needed.
Answer: Ti = −1.789 °C
Thermal resistance: steady heat flow through layers in series behaves like current through resistors in series: Q̇ = ΔT/ΣR, with R = L/(kA) for a conducting layer and R = 1/(hA) for a convecting surface. The temperature drop across each layer is proportional to its resistance.
The temperature drops across the first layer by Q̇·R₁.
Answer: U = 0.5839 W/(m²·K)
Thermal resistance: steady heat flow through layers in series behaves like current through resistors in series: Q̇ = ΔT/ΣR, with R = L/(kA) for a conducting layer and R = 1/(hA) for a convecting surface. The temperature drop across each layer is proportional to its resistance.
Answer: A = 52.23 m²
LMTD method: the temperature difference between the streams changes along the exchanger, so the rate equation uses its logarithmic mean: Q̇ = U·A·ΔTlm, with ΔTlm = (ΔT₁ − ΔT₂)/ln(ΔT₁/ΔT₂), where ΔT₁ and ΔT₂ are the differences at the two ends. Counter-flow gives a larger ΔTlm than parallel flow for the same inlet and outlet temperatures.
In counter-flow the hot inlet faces the cold outlet, and the hot outlet faces the cold inlet.
Answer: A = 3.422 m²
LMTD method: the temperature difference between the streams changes along the exchanger, so the rate equation uses its logarithmic mean: Q̇ = U·A·ΔTlm, with ΔTlm = (ΔT₁ − ΔT₂)/ln(ΔT₁/ΔT₂), where ΔT₁ and ΔT₂ are the differences at the two ends. Counter-flow gives a larger ΔTlm than parallel flow for the same inlet and outlet temperatures.
In counter-flow the hot inlet faces the cold outlet, and the hot outlet faces the cold inlet.
ExamProblems · examproblems.com/courses/heat-transfer