Heat conduction
- Fourier’s law
- Q̇ = kAΔT/L
- Conduction resistance
- R = L/(kA)
- Convection resistance
- R = 1/(hA)
- Resistances in series
- Q̇ = ΔTtotal/ΣR
- U-value
- U = 1/(ΣR·A)
Formula sheets, the key method steps for every topic and 4 practice problems, with full solutions at the back.
A wall is made of 100 mm of gypsum board and 50 mm of expanded polystyrene, with an area of 15 m². The outer faces are at 16 °C and 5 °C. Find the temperature Ti at the interface between the two layers.
A wall of 150 mm glass and 50 mm gypsum board separates a room at 22 °C from outside air at -13 °C. The convection coefficients are 6 W/(m²·K) inside and 30 W/(m²·K) outside, and the wall area is 20 m². Find the overall heat transfer coefficient U of the wall.
A counter-flow heat exchanger transfers 480 kW. Its heat transfer area is 4 m². The hot fluid cools from 180 to 145 °C and the cold fluid heats from 10 to 170 °C. Find the overall heat transfer coefficient U.
In a counter-flow heat exchanger both streams have the same heat capacity rate, ṁ·cp = 1 kW/K. The hot stream enters at 115 °C and the cold stream at 20 °C. The exchanger has A = 4 m² and U = 800 W/(m²·K). Find the hot outlet temperature Th,out.
Answer: Ti = 12.79 °C
Thermal resistance: steady heat flow through layers in series behaves like current through resistors in series: Q̇ = ΔT/ΣR, with R = L/(kA) for a conducting layer and R = 1/(hA) for a convecting surface. The temperature drop across each layer is proportional to its resistance.
The temperature drops across the first layer by Q̇·R₁.
Answer: U = 1.538 W/(m²·K)
Thermal resistance: steady heat flow through layers in series behaves like current through resistors in series: Q̇ = ΔT/ΣR, with R = L/(kA) for a conducting layer and R = 1/(hA) for a convecting surface. The temperature drop across each layer is proportional to its resistance.
Answer: U = 2499 W/(m²·K)
LMTD method: the temperature difference between the streams changes along the exchanger, so the rate equation uses its logarithmic mean: Q̇ = U·A·ΔTlm, with ΔTlm = (ΔT₁ − ΔT₂)/ln(ΔT₁/ΔT₂), where ΔT₁ and ΔT₂ are the differences at the two ends. Counter-flow gives a larger ΔTlm than parallel flow for the same inlet and outlet temperatures.
In counter-flow the hot inlet faces the cold outlet, and the hot outlet faces the cold inlet.
Answer: Th,out = 42.62 °C
LMTD method: the temperature difference between the streams changes along the exchanger, so the rate equation uses its logarithmic mean: Q̇ = U·A·ΔTlm, with ΔTlm = (ΔT₁ − ΔT₂)/ln(ΔT₁/ΔT₂), where ΔT₁ and ΔT₂ are the differences at the two ends. Counter-flow gives a larger ΔTlm than parallel flow for the same inlet and outlet temperatures.
The cold outlet sits opposite the hot inlet: Tc,out = Tc,in + (Th,in − Th,out), so ΔT₁ = Th,in − Tc,out = Th,out − Tc,in = ΔT₂.
Heat transferred: Q̇ = 72.38 kW; the cold stream leaves at 92.38 °C.
ExamProblems · examproblems.com/courses/heat-transfer