Heat Transfer: cram pack

Formula sheets, the key method steps for every topic and 4 practice problems, with full solutions at the back.

New problemsBack to the course

In the print window, choose “Save as PDF” to keep a copy on your device.

1Formulas and methods

Heat conduction

Fourier’s law
Q̇ = kAΔT/L
Conduction resistance
R = L/(kA)
Convection resistance
R = 1/(hA)
Resistances in series
Q̇ = ΔTtotal/ΣR
U-value
U = 1/(ΣR·A)

Heat exchangers (LMTD)

Heat duty
Q = U·A·ΔTlm
Log mean temperature difference
ΔTlm = (ΔT1 − ΔT2)/ln(ΔT1/ΔT2)
Stream balance
Q = ṁcp(Tin − Tout)

2Practice problems

1.Heat conductionMedium
Expanded polystyrene, k = 0.035200 mmBrick, k = 0.7275 mm22 °C-4 °CTi​ = ?Q̇

A wall is made of 200 mm of expanded polystyrene and 75 mm of brick, with an area of 20 m². The outer faces are at 22 °C and -4 °C. Find the temperature Ti at the interface between the two layers.

L1 = 200 mm, k1 = 0.035 W/(m·K)L2 = 75 mm, k2 = 0.72 W/(m·K)A = 20 m²T1 = 22 °CT3 = -4 °C
Ti = °C
2.Heat conductionHard
Gypsum board, k = 0.17150 mmGlass, k = 0.9625 mmroom 21 °Coutside -1 °CQ̇

A wall of 150 mm gypsum board and 25 mm glass separates a room at 21 °C from outside air at -1 °C. The convection coefficients are 8 W/(m²·K) inside and 25 W/(m²·K) outside, and the wall area is 20 m². Find the overall heat transfer coefficient U of the wall.

L1 = 150 mm, k1 = 0.17 W/(m·K)L2 = 25 mm, k2 = 0.96 W/(m·K)A = 20 m²hi = 8 W/(m²·K)ho = 25 W/(m²·K)Troom = 21 °CTout = -1 °C
U = W/(m²·K)
3.Heat exchangers (LMTD)Medium
lengthT110 °C40 °C85 °C20 °CΔT₁ΔT₂counter-flow

A counter-flow heat exchanger transfers 420 kW. The hot fluid cools from 110 to 40 °C and the cold fluid heats from 20 to 85 °C. The overall heat transfer coefficient is 500 W/(m²·K). Find the heat transfer area A needed.

Q̇ = 420 kWU = 500 W/(m²·K)Th: 110 → 40 °CTc: 20 → 85 °C
A = m²
4.Heat exchangers (LMTD)Hard
lengthT115 °C45 °C39.26 °C20 °CΔT₁ΔT₂counter-flow

Hot oil (1 kg/s, cp = 2.3 kJ/(kg·K)) cools from 115 to 45 °C in a counter-flow exchanger. It heats 2 kg/s of water (cp = 4.18 kJ/(kg·K)) that enters at 20 °C. With U = 1000 W/(m²·K), find the heat transfer area A needed.

ṁh = 1 kg/scp,h = 2.3 kJ/(kg·K)Th: 115 → 45 °Cṁc = 2 kg/scp,c = 4.18 kJ/(kg·K)Tc,in = 20 °CU = 1000 W/(m²·K)
A = m²

3Solutions

1.Heat conduction

Answer: Ti = −3.535 °C

Thermal resistance: steady heat flow through layers in series behaves like current through resistors in series: Q̇ = ΔT/ΣR, with R = L/(kA) for a conducting layer and R = 1/(hA) for a convecting surface. The temperature drop across each layer is proportional to its resistance.

Layer resistances

R1 = L1/(k1A) = (200/1000)/(0.035·20) = 0.2857 K/W
R2 = L2/(k2A) = (75/1000)/(0.72·20) = 0.005208 K/W

Heat flow

Q̇ = (T1 − T3)/(R1 + R2) = 26/0.2909 = 89.37 W

Interface temperature

The temperature drops across the first layer by Q̇·R₁.

Ti = T1 − Q̇·R1 = 22 − 89.37·0.2857 = −3.535 °C

Answer

Ti = −3.535 °C
2.Heat conduction

Answer: U = 0.9316 W/(m²·K)

Thermal resistance: steady heat flow through layers in series behaves like current through resistors in series: Q̇ = ΔT/ΣR, with R = L/(kA) for a conducting layer and R = 1/(hA) for a convecting surface. The temperature drop across each layer is proportional to its resistance.

Resistances in series

Ri = 1/(hiA) = 1/(8·20) = 0.00625 K/W
R1 = L1/(k1A) = (150/1000)/(0.17·20) = 0.04412 K/W
R2 = L2/(k2A) = (25/1000)/(0.96·20) = 0.001302 K/W
Ro = 1/(hoA) = 1/(25·20) = 0.002 K/W
ΣR = 0.05367 K/W

Overall coefficient

U = 1/(A·ΣR) = 1/(20·0.05367) = 0.9316 W/(m²·K)

Answer

U = 0.9316 W/(m²·K)
3.Heat exchangers (LMTD)

Answer: A = 37.49 m²

LMTD method: the temperature difference between the streams changes along the exchanger, so the rate equation uses its logarithmic mean: Q̇ = U·A·ΔTlm, with ΔTlm = (ΔT₁ − ΔT₂)/ln(ΔT₁/ΔT₂), where ΔT₁ and ΔT₂ are the differences at the two ends. Counter-flow gives a larger ΔTlm than parallel flow for the same inlet and outlet temperatures.

End temperature differences

In counter-flow the hot inlet faces the cold outlet, and the hot outlet faces the cold inlet.

ΔT₁ = Th,in − Tc,out = 110 − 85 = 25 K
ΔT₂ = Th,out − Tc,in = 40 − 20 = 20 K

Log-mean temperature difference

ΔTlm = (ΔT₁ − ΔT₂)/ln(ΔT₁/ΔT₂) = (25 − 20)/ln(25/20) = 22.41 K

Area

A = Q̇/(U·ΔTlm) = 420000/(500·22.41) = 37.49 m²

Answer

A = 37.49 m²
4.Heat exchangers (LMTD)

Answer: A = 3.517 m²

LMTD method: the temperature difference between the streams changes along the exchanger, so the rate equation uses its logarithmic mean: Q̇ = U·A·ΔTlm, with ΔTlm = (ΔT₁ − ΔT₂)/ln(ΔT₁/ΔT₂), where ΔT₁ and ΔT₂ are the differences at the two ends. Counter-flow gives a larger ΔTlm than parallel flow for the same inlet and outlet temperatures.

Heat duty and water outlet temperature

Q̇ = ṁhcp,h(Th,in − Th,out) = 1·2.3·70 = 161 kW
Tc,out = 20 + 161/(2·4.18) = 39.26 °C

End temperature differences

In counter-flow the hot inlet faces the cold outlet, and the hot outlet faces the cold inlet.

ΔT₁ = Th,in − Tc,out = 115 − 39.26 = 75.74 K
ΔT₂ = Th,out − Tc,in = 45 − 20 = 25 K

Log-mean temperature difference

ΔTlm = (ΔT₁ − ΔT₂)/ln(ΔT₁/ΔT₂) = (75.74 − 25)/ln(75.74/25) = 45.78 K

Area

A = Q̇/(U·ΔTlm) = 161000/(1000·45.78) = 3.517 m²

Answer

A = 3.517 m²

ExamProblems · examproblems.com/courses/heat-transfer