Heat Transfer: cram pack

Formula sheets, the key method steps for every topic and 4 practice problems, with full solutions at the back.

New problemsBack to the course

In the print window, choose “Save as PDF” to keep a copy on your device.

1Formulas and methods

Heat conduction

Fourier’s law
Q̇ = kAΔT/L
Conduction resistance
R = L/(kA)
Convection resistance
R = 1/(hA)
Resistances in series
Q̇ = ΔTtotal/ΣR
U-value
U = 1/(ΣR·A)

Heat exchangers (LMTD)

Heat duty
Q = U·A·ΔTlm
Log mean temperature difference
ΔTlm = (ΔT1 − ΔT2)/ln(ΔT1/ΔT2)
Stream balance
Q = ṁcp(Tin − Tout)

2Practice problems

1.Heat conductionMedium
Brick, k = 0.72150 mmWood, k = 0.17150 mm21 °C-4 °CTi​ = ?Q̇

A wall is made of 150 mm of brick and 150 mm of wood, with an area of 4 m². The outer faces are at 21 °C and -4 °C. Find the temperature Ti at the interface between the two layers.

L1 = 150 mm, k1 = 0.72 W/(m·K)L2 = 150 mm, k2 = 0.17 W/(m·K)A = 4 m²T1 = 21 °CT3 = -4 °C
Ti = °C
2.Heat conductionHard
Brick, k = 0.7250 mmWood, k = 0.1775 mmroom 20 °Coutside 0 °CTs​ = ?Q̇

A wall of 50 mm brick and 75 mm wood separates a room at 20 °C from outside air at 0 °C. The convection coefficients are 6 W/(m²·K) inside and 25 W/(m²·K) outside, and the wall area is 12 m². Find the temperature Ts of the inside surface of the wall.

L1 = 50 mm, k1 = 0.72 W/(m·K)L2 = 75 mm, k2 = 0.17 W/(m·K)A = 12 m²hi = 6 W/(m²·K)ho = 25 W/(m²·K)Troom = 20 °CTout = 0 °C
Ts = °C
3.Heat exchangers (LMTD)Medium
lengthT140 °C25 °C75 °CΔT₁ΔT₂condensing steam

In a condenser, steam condenses at a constant 140 °C on the outside of the tubes. Cooling water (1 kg/s, cp = 4.18 kJ/(kg·K)) flows through the tubes and heats from 25 to 75 °C. The overall heat transfer coefficient is 3500 W/(m²·K). Find the heat transfer area A needed.

Ts = 140 °Cṁ = 1 kg/scp = 4.18 kJ/(kg·K)Tc: 25 → 75 °CU = 3500 W/(m²·K)
A = m²
4.Heat exchangers (LMTD)Hard
lengthT160 °C??20 °CΔT₁ΔT₂counter-flow

In a counter-flow heat exchanger both streams have the same heat capacity rate, ṁ·cp = 1.5 kW/K. The hot stream enters at 160 °C and the cold stream at 20 °C. The exchanger has A = 3 m² and U = 800 W/(m²·K). Find the hot outlet temperature Th,out.

Ch = Cc = 1.5 kW/KTh,in = 160 °CTc,in = 20 °CA = 3 m²U = 800 W/(m²·K)
Th,out = °C

3Solutions

1.Heat conduction

Answer: Ti = 16.22 °C

Thermal resistance: steady heat flow through layers in series behaves like current through resistors in series: Q̇ = ΔT/ΣR, with R = L/(kA) for a conducting layer and R = 1/(hA) for a convecting surface. The temperature drop across each layer is proportional to its resistance.

Layer resistances

R1 = L1/(k1A) = (150/1000)/(0.72·4) = 0.05208 K/W
R2 = L2/(k2A) = (150/1000)/(0.17·4) = 0.2206 K/W

Heat flow

Q̇ = (T1 − T3)/(R1 + R2) = 25/0.2727 = 91.69 W

Interface temperature

The temperature drops across the first layer by Q̇·R₁.

Ti = T1 − Q̇·R1 = 21 − 91.69·0.05208 = 16.22 °C

Answer

Ti = 16.22 °C
2.Heat conduction

Answer: Ts = 15.35 °C

Thermal resistance: steady heat flow through layers in series behaves like current through resistors in series: Q̇ = ΔT/ΣR, with R = L/(kA) for a conducting layer and R = 1/(hA) for a convecting surface. The temperature drop across each layer is proportional to its resistance.

Resistances in series

Ri = 1/(hiA) = 1/(6·12) = 0.01389 K/W
R1 = L1/(k1A) = (50/1000)/(0.72·12) = 0.005787 K/W
R2 = L2/(k2A) = (75/1000)/(0.17·12) = 0.03676 K/W
Ro = 1/(hoA) = 1/(25·12) = 0.003333 K/W
ΣR = 0.05977 K/W

Heat loss

Q̇ = (20 − (0))/0.05977 = 334.6 W
Ts = Troom − Q̇·Ri = 20 − 334.6·0.01389 = 15.35 °C

Answer

Ts = 15.35 °C
3.Heat exchangers (LMTD)

Answer: A = 0.6814 m²

LMTD method: the temperature difference between the streams changes along the exchanger, so the rate equation uses its logarithmic mean: Q̇ = U·A·ΔTlm, with ΔTlm = (ΔT₁ − ΔT₂)/ln(ΔT₁/ΔT₂), where ΔT₁ and ΔT₂ are the differences at the two ends. Counter-flow gives a larger ΔTlm than parallel flow for the same inlet and outlet temperatures.

Heat duty from the water side

Q̇ = 1·4.18·(75 − 25) = 209 kW

End temperature differences

ΔT₁ = 140 − 25 = 115 K
ΔT₂ = 140 − 75 = 65 K

Log-mean temperature difference

ΔTlm = (ΔT₁ − ΔT₂)/ln(ΔT₁/ΔT₂) = (115 − 65)/ln(115/65) = 87.64 K

Area

A = Q̇/(U·ΔTlm) = 209000/(3500·87.64) = 0.6814 m²

Answer

A = 0.6814 m²
4.Heat exchangers (LMTD)

Answer: Th,out = 73.85 °C

LMTD method: the temperature difference between the streams changes along the exchanger, so the rate equation uses its logarithmic mean: Q̇ = U·A·ΔTlm, with ΔTlm = (ΔT₁ − ΔT₂)/ln(ΔT₁/ΔT₂), where ΔT₁ and ΔT₂ are the differences at the two ends. Counter-flow gives a larger ΔTlm than parallel flow for the same inlet and outlet temperatures.

Constant temperature difference

The cold outlet sits opposite the hot inlet: Tc,out = Tc,in + (Th,in − Th,out), so ΔT₁ = Th,in − Tc,out = Th,out − Tc,in = ΔT₂.

ΔTlm = Th,out − Tc,in

Energy balance equals rate equation

1.5·(160 − Th,out) = 2.4·(Th,out − 20)
Th,out = (1.5·160 + 2.4·20)/(1.5 + 2.4) = 73.85 °C

Answer

Th,out = 73.85 °C

Heat transferred: Q̇ = 129.2 kW; the cold stream leaves at 106.2 °C.

ExamProblems · examproblems.com/courses/heat-transfer