Heat conduction
- Fourier’s law
- Q̇ = kAΔT/L
- Conduction resistance
- R = L/(kA)
- Convection resistance
- R = 1/(hA)
- Resistances in series
- Q̇ = ΔTtotal/ΣR
- U-value
- U = 1/(ΣR·A)
Formula sheets, the key method steps for every topic and 4 practice problems, with full solutions at the back.
A wall is made of 50 mm of expanded polystyrene and 50 mm of concrete, with an area of 12 m². The outer faces are at 17 °C and 10 °C. Find the heat flow Q̇ through the wall.
A wall of 150 mm gypsum board and 75 mm concrete separates a room at 21 °C from outside air at -8 °C. The convection coefficients are 10 W/(m²·K) inside and 25 W/(m²·K) outside, and the wall area is 6 m². Find the heat loss Q̇ through the wall.
A counter-flow heat exchanger transfers 50 kW. Its heat transfer area is 6 m². The hot fluid cools from 125 to 65 °C and the cold fluid heats from 15 to 95 °C. Find the overall heat transfer coefficient U.
Hot oil (0.5 kg/s, cp = 2.5 kJ/(kg·K)) cools from 80 to 45 °C in a counter-flow exchanger. It heats 3 kg/s of water (cp = 4.18 kJ/(kg·K)) that enters at 25 °C. With U = 1000 W/(m²·K), find the heat transfer area A needed.
Answer: Q̇ = 57.37 W
Thermal resistance: steady heat flow through layers in series behaves like current through resistors in series: Q̇ = ΔT/ΣR, with R = L/(kA) for a conducting layer and R = 1/(hA) for a convecting surface. The temperature drop across each layer is proportional to its resistance.
Answer: Q̇ = 161.7 W
Thermal resistance: steady heat flow through layers in series behaves like current through resistors in series: Q̇ = ΔT/ΣR, with R = L/(kA) for a conducting layer and R = 1/(hA) for a convecting surface. The temperature drop across each layer is proportional to its resistance.
Answer: U = 212.8 W/(m²·K)
LMTD method: the temperature difference between the streams changes along the exchanger, so the rate equation uses its logarithmic mean: Q̇ = U·A·ΔTlm, with ΔTlm = (ΔT₁ − ΔT₂)/ln(ΔT₁/ΔT₂), where ΔT₁ and ΔT₂ are the differences at the two ends. Counter-flow gives a larger ΔTlm than parallel flow for the same inlet and outlet temperatures.
In counter-flow the hot inlet faces the cold outlet, and the hot outlet faces the cold inlet.
Answer: A = 1.314 m²
LMTD method: the temperature difference between the streams changes along the exchanger, so the rate equation uses its logarithmic mean: Q̇ = U·A·ΔTlm, with ΔTlm = (ΔT₁ − ΔT₂)/ln(ΔT₁/ΔT₂), where ΔT₁ and ΔT₂ are the differences at the two ends. Counter-flow gives a larger ΔTlm than parallel flow for the same inlet and outlet temperatures.
In counter-flow the hot inlet faces the cold outlet, and the hot outlet faces the cold inlet.
ExamProblems · examproblems.com/courses/heat-transfer