Heat Transfer: cram pack

Formula sheets, the key method steps for every topic and 4 practice problems, with full solutions at the back.

New problemsBack to the course

In the print window, choose “Save as PDF” to keep a copy on your device.

1Formulas and methods

Heat conduction

Fourier’s law
Q̇ = kAΔT/L
Conduction resistance
R = L/(kA)
Convection resistance
R = 1/(hA)
Resistances in series
Q̇ = ΔTtotal/ΣR
U-value
U = 1/(ΣR·A)

Heat exchangers (LMTD)

Heat duty
Q = U·A·ΔTlm
Log mean temperature difference
ΔTlm = (ΔT1 − ΔT2)/ln(ΔT1/ΔT2)
Stream balance
Q = ṁcp(Tin − Tout)

2Practice problems

1.Heat conductionMedium
Mineral wool, k = 0.0450 mmConcrete, k = 1.450 mm21 °C3 °CQ̇ = ?

A wall is made of 50 mm of mineral wool and 50 mm of concrete, with an area of 15 m². The outer faces are at 21 °C and 3 °C. Find the heat flow Q̇ through the wall.

L1 = 50 mm, k1 = 0.04 W/(m·K)L2 = 50 mm, k2 = 1.4 W/(m·K)A = 15 m²T1 = 21 °CT3 = 3 °C
Q̇ = W
2.Heat conductionHard
Mineral wool, k = 0.04100 mmExpanded polystyrene, k = 0.035150 mmroom 21 °Coutside -1 °CQ̇

A wall of 100 mm mineral wool and 150 mm expanded polystyrene separates a room at 21 °C from outside air at -1 °C. The convection coefficients are 8 W/(m²·K) inside and 20 W/(m²·K) outside, and the wall area is 6 m². Find the overall heat transfer coefficient U of the wall.

L1 = 100 mm, k1 = 0.04 W/(m·K)L2 = 150 mm, k2 = 0.035 W/(m·K)A = 6 m²hi = 8 W/(m²·K)ho = 20 W/(m²·K)Troom = 21 °CTout = -1 °C
U = W/(m²·K)
3.Heat exchangers (LMTD)Medium
lengthT100 °C80 °C20 °C60 °CΔT₁ΔT₂parallel flow

A parallel-flow heat exchanger transfers 220 kW. The hot fluid cools from 100 to 80 °C and the cold fluid heats from 20 to 60 °C. The overall heat transfer coefficient is 1000 W/(m²·K). Find the heat transfer area A needed.

Q̇ = 220 kWU = 1000 W/(m²·K)Th: 100 → 80 °CTc: 20 → 60 °C
A = m²
4.Heat exchangers (LMTD)Hard
lengthT105 °C75 °C?25 °CΔT₁ΔT₂counter-flow

In a counter-flow double-pipe heat exchanger, hot oil (0.2 kg/s, cp = 2.3 kJ/(kg·K)) flows in the inner tube and cools from 105 to 75 °C. Water (0.5 kg/s, cp = 4.18 kJ/(kg·K)) in the annulus enters at 25 °C. The inner tube has a diameter of 40 mm, and U = 500 W/(m²·K) is based on this diameter. Find the tube length L needed.

ṁh = 0.2 kg/scp,h = 2.3 kJ/(kg·K)Th: 105 → 75 °Cṁc = 0.5 kg/sTc,in = 25 °CD = 40 mmU = 500 W/(m²·K)
L = m

3Solutions

1.Heat conduction

Answer: Q̇ = 210 W

Thermal resistance: steady heat flow through layers in series behaves like current through resistors in series: Q̇ = ΔT/ΣR, with R = L/(kA) for a conducting layer and R = 1/(hA) for a convecting surface. The temperature drop across each layer is proportional to its resistance.

Layer resistances

R1 = L1/(k1A) = (50/1000)/(0.04·15) = 0.08333 K/W
R2 = L2/(k2A) = (50/1000)/(1.4·15) = 0.002381 K/W

Heat flow

Q̇ = (T1 − T3)/(R1 + R2) = 18/0.08571 = 210 W

Answer

Q̇ = 210 W
2.Heat conduction

Answer: U = 0.1437 W/(m²·K)

Thermal resistance: steady heat flow through layers in series behaves like current through resistors in series: Q̇ = ΔT/ΣR, with R = L/(kA) for a conducting layer and R = 1/(hA) for a convecting surface. The temperature drop across each layer is proportional to its resistance.

Resistances in series

Ri = 1/(hiA) = 1/(8·6) = 0.02083 K/W
R1 = L1/(k1A) = (100/1000)/(0.04·6) = 0.4167 K/W
R2 = L2/(k2A) = (150/1000)/(0.035·6) = 0.7143 K/W
Ro = 1/(hoA) = 1/(20·6) = 0.008333 K/W
ΣR = 1.16 K/W

Overall coefficient

U = 1/(A·ΣR) = 1/(6·1.16) = 0.1437 W/(m²·K)

Answer

U = 0.1437 W/(m²·K)
3.Heat exchangers (LMTD)

Answer: A = 5.083 m²

LMTD method: the temperature difference between the streams changes along the exchanger, so the rate equation uses its logarithmic mean: Q̇ = U·A·ΔTlm, with ΔTlm = (ΔT₁ − ΔT₂)/ln(ΔT₁/ΔT₂), where ΔT₁ and ΔT₂ are the differences at the two ends. Counter-flow gives a larger ΔTlm than parallel flow for the same inlet and outlet temperatures.

End temperature differences

In parallel flow both inlets are at the same end, and both outlets at the other.

ΔT₁ = Th,in − Tc,in = 100 − 20 = 80 K
ΔT₂ = Th,out − Tc,out = 80 − 60 = 20 K

Log-mean temperature difference

ΔTlm = (ΔT₁ − ΔT₂)/ln(ΔT₁/ΔT₂) = (80 − 20)/ln(80/20) = 43.28 K

Area

A = Q̇/(U·ΔTlm) = 220000/(1000·43.28) = 5.083 m²

Answer

A = 5.083 m²
4.Heat exchangers (LMTD)

Answer: L = 3.603 m

LMTD method: the temperature difference between the streams changes along the exchanger, so the rate equation uses its logarithmic mean: Q̇ = U·A·ΔTlm, with ΔTlm = (ΔT₁ − ΔT₂)/ln(ΔT₁/ΔT₂), where ΔT₁ and ΔT₂ are the differences at the two ends. Counter-flow gives a larger ΔTlm than parallel flow for the same inlet and outlet temperatures.

Heat duty and water outlet temperature

Q̇ = 0.2·2.3·(105 − 75) = 13.8 kW
Tc,out = 25 + 13.8/(0.5·4.18) = 31.6 °C

End temperature differences

In counter-flow the hot inlet faces the cold outlet, and the hot outlet faces the cold inlet.

ΔT₁ = Th,in − Tc,out = 105 − 31.6 = 73.4 K
ΔT₂ = Th,out − Tc,in = 75 − 25 = 50 K

Log-mean temperature difference

ΔTlm = (ΔT₁ − ΔT₂)/ln(ΔT₁/ΔT₂) = (73.4 − 50)/ln(73.4/50) = 60.95 K

Area and length

A = 13800/(500·60.95) = 0.4528 m²
L = A/(πD) = 0.4528/(π·0.04) = 3.603 m

Answer

L = 3.603 m

ExamProblems · examproblems.com/courses/heat-transfer