Power Systems and Electrical Machines: cram pack

Formula sheets, the key method steps for every topic and 10 practice problems, with full solutions at the back.

New problemsBack to the course

In the print window, choose “Save as PDF” to keep a copy on your device.

1Formulas and methods

Three-phase power

Y connection
VL = √3·Vph, IL = Iph
Δ connection
VL = Vph, IL = √3·Iph
Total real power
P = √3·VL·IL·cos φ = 3·Iph²·R
Apparent and reactive power
S = √3·VL·IL, Q = P·tan φ
Correction capacitors
QC = P(tan φ1 − tan φ2), C = QC/(3ωV²)
Voltage across each capacitor
Δ: VL Y: VL/√3
Motor input
Pin = Pout/η

Transformers

Turns ratio
a = N1/N2 = V1/V2
Current ratio
I1/I2 = N2/N1 = 1/a
Rated current
I = S/V
Referred impedance
Z1′ = a²·ZL
Copper loss at part load
Pcu = x²·Pcu,fl
Efficiency
η = x·S·pf/(x·S·pf + Pcore + x²·Pcu,fl)
Maximum efficiency
x = √(Pcore/Pcu,fl)

AC power & power factor

Real power
P = V·I·cos φ
Reactive power
Q = V·I·sin φ
Apparent power
S = V·I = √(P² + Q²)
Power factor
pf = cos φ = P/S
Correction capacitor
QC = P(tan φ1 − tan φ2), C = QC/(ωV²)

AC impedance & phasors

Impedances
ZR = R, ZL = jωL, ZC = 1/(jωC)
Angular frequency
ω = 2πf
Magnitude and angle
|Z| = √(R² + X²), φ = atan(X/R)
Phasor Ohm’s law
V = I·Z

Method

  1. Convert the frequency: ω = 2πf.
  2. Find each reactance: XL = ωL and XC = 1/(ωC).
  3. Add impedances like resistors, with Z = R + jX.
  4. Find the magnitude |Z| = √(R² + X²) and the angle φ = atan(X/R), then use Ohm’s law with phasors.

DC motors

Armature circuit
V = E + IaRa
Back-EMF and torque
E = k·ω, T = k·Ia
Speed
ω = 2π·n/60, ω = (V − IaRa)/k
No-load speed and stall torque
ω0 = V/k, Tstall = k·V/Ra
Powers
Pin = V·Ia, Pdev = E·Ia = T·ω, Pout = Pdev − Prot
Starting
Istart = V/(Ra + Rst)
Speed regulation
SR = (n0 − nFL)/nFL
Maximum developed power
Pmax = V²/(4Ra)
Chopper drive
Va = D·Vdc

Method

  1. Draw the armature circuit: supply V, resistance Ra and the back-EMF E in series.
  2. Use V = E + Ia·Ra to link voltage, current and back-EMF.
  3. Use E = k·ω for speed and T = k·Ia for torque, with ω = 2π·n/60.
  4. For power and efficiency, start from V·Ia, subtract the copper loss Ia²·Ra and then the rotational losses.

2Practice problems

1.Three-phase powerMedium
ABCVL​ = 415 VIL​ = 12 Acos φ = 0.8lagging

A balanced three-phase load draws a line current of 12 A from a supply with a line-to-line voltage of 415 V. The power factor is 0.8 lagging. Find the total real power P drawn by the load in kW.

VL = 415 VIL = 12 Acos φ = 0.8
P = kW
2.Three-phase powerHard
P = 50 kWφ1​S1​Q2​QC​

A balanced three-phase load takes 50 kW at a power factor of 0.78 lagging from a 415 V (line-to-line), 50 Hz supply. A three-phase capacitor bank in parallel with the load must raise the overall power factor to 0.9 lagging. The real power stays the same. The capacitors are connected in Y. Find the capacitance Cph of each capacitor in µF.

P = 50 kWpf1 = 0.78pf2 = 0.9VL = 415 Vf = 50 Hz
Cph = µF
3.TransformersMedium
6600 V230 VIHV​ILV​ = ?75 kVA

A single-phase 75 kVA, 6600/230 V transformer operates at its rated load. Treat it as ideal. Find the current ILV in the low-voltage winding.

S = 75 kVAV1 = 6600 VV2 = 230 V
ILV = A
4.TransformersHard
pf 0.9525 kVA, 75% load

A single-phase 25 kVA transformer has a core loss of 150 W and a copper loss of 225 W at rated load. It supplies 75% of its rated kVA at a power factor of 0.95 lagging. Find the total losses Ploss in watts at this load.

S = 25 kVAPcore = 150 WPcu,fl = 225 Wx = 0.75pf = 0.95
Ploss = W
5.AC power & power factorMedium
120 VR + jXP = 690 W11.5 A

An inductive load takes 11.5 A and 690 W from a 120 V (rms) single-phase supply. Model it as a resistance R in series with a reactance X. Find X.

V = 120 VI = 11.5 AP = 690 W
X = Ω
6.AC power & power factorHard
240 V50 Hzload7 kW, 0.8C47 µFI

A single-phase load takes 7 kW at a power factor of 0.8 lagging from a 240 V, 50 Hz supply. A 47 µF capacitor is connected in parallel with the load. Find the new power factor cos φ seen by the supply.

P = 7 kWpf1 = 0.8V = 240 Vf = 50 HzC = 47 µF
cos φ =
7.AC impedance & phasorsMedium
50 V100 HzR = 100 ΩL = 50 mHC = 10 µFI

A series RLC circuit is connected to a 50 V (rms), 100 Hz supply. Find the real power P taken from the supply.

V = 50 V (rms)f = 100 HzR = 100 ΩL = 50 mHC = 10 µF
P = W
8.AC impedance & phasorsHard
230 V500 HzR = 40 ΩL = 50 mHC = 1 µF

A series RLC circuit is connected to a 230 V (rms), 500 Hz supply. Find the resonant frequency f0 of the circuit.

V = 230 V (rms)f = 500 HzR = 40 ΩL = 50 mHC = 1 µF
f0 = Hz
9.DC motorsMedium
+−240 VRa​ = 0.5 ΩIa​ = 30 AM+−EωT

A DC motor draws 30 A from a 240 V supply. Its armature resistance is 0.5 Ω and its rotational (friction, windage and iron) losses are 540 W. Find its efficiency η.

V = 240 VIa = 30 ARa = 0.5 ΩProt = 540 W
η = %
10.DC motorsHard
+−48 VRa​ = 1.5 ΩM+−EωT

A small DC motor has an armature resistance of 1.5 Ω and runs from 48 V. Neglecting rotational losses, find the largest mechanical power Pmax it can develop at any speed.

V = 48 VRa = 1.5 Ω
Pmax = W

3Solutions

1.Three-phase power

Answer: P = 6.9 kW

Balanced three-phase systems: in a Y (star) connection the line-to-line voltage is √3 times the phase voltage, VL = √3·Vph, and the line current equals the phase current. In a Δ (delta) connection the line-to-line voltage equals the phase voltage and the line current is √3 times the phase current, IL = √3·Iph. The total power is three times the power of one phase: P = 3·Vph·Iph·cos φ = √3·VL·IL·cos φ.

Apparent power

S = √3·VL·IL = √3·415·12 = 8.626 kVA

Real power

P = S·cos φ = 8.626·0.8 = 6.9 kW

Answer

P = 6.9 kW
2.Three-phase power

Answer: Cph = 293.8 µF

Balanced three-phase systems: in a Y (star) connection the line-to-line voltage is √3 times the phase voltage, VL = √3·Vph, and the line current equals the phase current. In a Δ (delta) connection the line-to-line voltage equals the phase voltage and the line current is √3 times the phase current, IL = √3·Iph. The total power is three times the power of one phase: P = 3·Vph·Iph·cos φ = √3·VL·IL·cos φ. Power factor correction: capacitors supply reactive power locally, QC = P·(tan φ1 − tan φ2). Each of the three capacitors supplies QC/3 = V²·ω·C, where V is the voltage across that capacitor: VL in a Δ bank, VL/√3 in a Y bank.

Reactive power before and after

The real power is unchanged, so each power factor fixes the reactive power: Q = P·tan φ.

Q1 = 50·tan(acos 0.78) = 50·0.8023 = 40.11 kvar
Q2 = 50·tan(acos 0.9) = 50·0.4843 = 24.22 kvar

Reactive power from the capacitors

QC = Q1 − Q2 = 15.9 kvar

Capacitance per phase

In a Y bank each capacitor is connected between a line and the star point.

V = 415/√3 = 239.6 V, ω = 2π·50 = 314.2 rad/s
Cph = (QC/3)/(ω·V²) = 5299/(314.2·239.6²) = 293.8 µF

Answer

Cph = 293.8 µF
3.Transformers

Answer: ILV = 326.1 A

Ideal transformer: the voltages are in the ratio of the turns and the currents in the inverse ratio: V₁/V₂ = N₁/N₂ = a and I₁/I₂ = N₂/N₁ = 1/a, so the power in equals the power out, V₁·I₁ = V₂·I₂. A load impedance Z on the secondary looks like a²·Z from the primary.

Rated current

Both windings carry the same apparent power.

ILV = S/V = 75000/230 = 326.1 A

Answer

ILV = 326.1 A
4.Transformers

Answer: Ploss = 276.6 W

Transformer losses: the core loss (hysteresis and eddy currents) depends on the voltage and is the same at any load. The copper loss in the windings goes with the current squared, so at a fraction x of rated load it is x²·Pcu,fl. Efficiency η = Pout/(Pout + Pcore + Pcu), with Pout = x·S·pf. The efficiency is highest at the load where the copper loss equals the core loss.

Copper loss at this load

Pcu = x²·Pcu,fl = 0.5625·225 = 126.6 W

Total losses

The core loss is the same at any load.

Ploss = 150 + 126.6 = 276.6 W

Answer

Ploss = 276.6 W

The efficiency at this load is η = 98.47%.

5.AC power & power factor

Answer: X = 9.037 Ω

AC power: apparent power S = V·I (VA) splits into real power P = S·cos φ (W), which does useful work, and reactive power Q = S·sin φ (var), which moves back and forth between source and load. The power factor is cos φ. A capacitor in parallel supplies reactive power locally, so the line current drops for the same real power.

Resistance from the real power

R = P/I² = 690/11.5² = 5.217 Ω

Reactance from the impedance

|Z| = V/I = 120/11.5 = 10.43 Ω
X = √(|Z|² − R²) = √(10.43² − 5.217²) = 9.037 Ω

Answer

X = 9.037 Ω
6.AC power & power factor

Answer: cos φ = 0.8467

AC power: apparent power S = V·I (VA) splits into real power P = S·cos φ (W), which does useful work, and reactive power Q = S·sin φ (var), which moves back and forth between source and load. The power factor is cos φ. A capacitor in parallel supplies reactive power locally, so the line current drops for the same real power.

Reactive power before and after

The real power P does not change; only the reactive power drawn from the supply does.

Q1 = 7·tan(arccos 0.8) = 5.25 kvar
QC = V²·2πf·C = 240²·2π·50·47·10⁻⁶ = 850.5 var = 0.8505 kvar
Q2 = 5.25 − 0.8505 = 4.4 kvar

New apparent power

S2 = √(7² + 4.4²) = 8.268 kVA

New power factor

cos φ = P/S2 = 7/8.268 = 0.8467

Answer

cos φ = 0.8467
7.AC impedance & phasors

Answer: P = 9.499 W

AC circuits with phasors: resistors, inductors and capacitors have impedances R, jωL and 1/(jωC), with ω = 2πf. In series, impedances add like resistances, but as complex numbers. Rms current and voltage follow Ohm’s law with |Z|.

Reactances

XL = 31.42 Ω, XC = 159.2 Ω

Impedance

|Z| = √(100² + (−127.7)²) = 162.2 Ω

Real power

Inductors and capacitors only store and return energy; the resistor absorbs all of the real power.

I = 50/162.2 = 0.3082 A
P = I²·R = 0.3082²·100 = 9.499 W

Answer

P = 9.499 W
8.AC impedance & phasors

Answer: f0 = 711.8 Hz

AC circuits with phasors: resistors, inductors and capacitors have impedances R, jωL and 1/(jωC), with ω = 2πf. In series, impedances add like resistances, but as complex numbers. Rms current and voltage follow Ohm’s law with |Z|.

Resonance

At resonance the inductive and capacitive reactances cancel: ωL = 1/(ωC). The supply frequency does not matter.

f0 = 1/(2π√(LC)) = 1/(2π·√(0.05·1·10⁻⁶)) = 711.8 Hz

Answer

f0 = 711.8 Hz
9.DC motors

Answer: η = 86.25 %

DC motor: the armature is a resistance Ra in series with the back-EMF E, so V = E + Ia·Ra. The back-EMF grows with speed, E = k·ω, and the torque with current, T = k·Ia, with the same motor constant k (V·s/rad = N·m/A) in SI units. Convert speeds with ω = 2π·n/60. The developed power is E·Ia = T·ω; the input power is V·Ia, and the copper loss Ia²Ra and the rotational loss make the difference. The speed falls in a straight line with torque, ω = V/k − Ra·T/k², from the no-load speed V/k to zero at the stall torque k·V/Ra. At standstill E = 0, so the starting current V/Ra is large unless a resistor limits it.

Powers

Pin = 240·30 = 7200 W
Pdev = 225·30 = 6750 W
Pout = 6750 − 540 = 6210 W

Efficiency

η = 6210/7200·100 = 86.25 %

Answer

η = 86.25 %
10.DC motors

Answer: Pmax = 384 W

DC motor: the armature is a resistance Ra in series with the back-EMF E, so V = E + Ia·Ra. The back-EMF grows with speed, E = k·ω, and the torque with current, T = k·Ia, with the same motor constant k (V·s/rad = N·m/A) in SI units. Convert speeds with ω = 2π·n/60. The developed power is E·Ia = T·ω; the input power is V·Ia, and the copper loss Ia²Ra and the rotational loss make the difference. The speed falls in a straight line with torque, ω = V/k − Ra·T/k², from the no-load speed V/k to zero at the stall torque k·V/Ra. At standstill E = 0, so the starting current V/Ra is large unless a resistor limits it.

Power as a function of the back-EMF

P(E) = E·(V − E)/Ra
dP/dE = 0 → E = V/2 = 24 V

Maximum power

Pmax = (V/2)²/Ra = V²/(4Ra) = 48²/(4·1.5) = 384 W

Answer

Pmax = 384 W

At this point the efficiency is only 50 %, so real motors run well above half speed.

ExamProblems · examproblems.com/courses/power-systems