Power Systems and Electrical Machines: cram pack

Formula sheets, the key method steps for every topic and 10 practice problems, with full solutions at the back.

New problemsBack to the course

In the print window, choose “Save as PDF” to keep a copy on your device.

1Formulas and methods

Three-phase power

Y connection
VL = √3·Vph, IL = Iph
Δ connection
VL = Vph, IL = √3·Iph
Total real power
P = √3·VL·IL·cos φ = 3·Iph²·R
Apparent and reactive power
S = √3·VL·IL, Q = P·tan φ
Correction capacitors
QC = P(tan φ1 − tan φ2), C = QC/(3ωV²)
Voltage across each capacitor
Δ: VL Y: VL/√3
Motor input
Pin = Pout/η

Transformers

Turns ratio
a = N1/N2 = V1/V2
Current ratio
I1/I2 = N2/N1 = 1/a
Rated current
I = S/V
Referred impedance
Z1′ = a²·ZL
Copper loss at part load
Pcu = x²·Pcu,fl
Efficiency
η = x·S·pf/(x·S·pf + Pcore + x²·Pcu,fl)
Maximum efficiency
x = √(Pcore/Pcu,fl)

AC power & power factor

Real power
P = V·I·cos φ
Reactive power
Q = V·I·sin φ
Apparent power
S = V·I = √(P² + Q²)
Power factor
pf = cos φ = P/S
Correction capacitor
QC = P(tan φ1 − tan φ2), C = QC/(ωV²)

AC impedance & phasors

Impedances
ZR = R, ZL = jωL, ZC = 1/(jωC)
Angular frequency
ω = 2πf
Magnitude and angle
|Z| = √(R² + X²), φ = atan(X/R)
Phasor Ohm’s law
V = I·Z

Method

  1. Convert the frequency: ω = 2πf.
  2. Find each reactance: XL = ωL and XC = 1/(ωC).
  3. Add impedances like resistors, with Z = R + jX.
  4. Find the magnitude |Z| = √(R² + X²) and the angle φ = atan(X/R), then use Ohm’s law with phasors.

DC motors

Armature circuit
V = E + IaRa
Back-EMF and torque
E = k·ω, T = k·Ia
Speed
ω = 2π·n/60, ω = (V − IaRa)/k
No-load speed and stall torque
ω0 = V/k, Tstall = k·V/Ra
Powers
Pin = V·Ia, Pdev = E·Ia = T·ω, Pout = Pdev − Prot
Starting
Istart = V/(Ra + Rst)
Speed regulation
SR = (n0 − nFL)/nFL
Maximum developed power
Pmax = V²/(4Ra)
Chopper drive
Va = D·Vdc

Method

  1. Draw the armature circuit: supply V, resistance Ra and the back-EMF E in series.
  2. Use V = E + Ia·Ra to link voltage, current and back-EMF.
  3. Use E = k·ω for speed and T = k·Ia for torque, with ω = 2π·n/60.
  4. For power and efficiency, start from V·Ia, subtract the copper loss Ia²·Ra and then the rotational losses.

2Practice problems

1.Three-phase powerMedium
ABCVL​ = 480 VIL​ = 30 Acos φ = 0.88lagging

A balanced three-phase load draws a line current of 30 A from a supply with a line-to-line voltage of 480 V. The power factor is 0.88 lagging. Find the total real power P drawn by the load in kW.

VL = 480 VIL = 30 Acos φ = 0.88
P = kW
2.Three-phase powerHard
P = 300 kWφ1​S1​Q2​QC​

A balanced three-phase load takes 300 kW at a power factor of 0.7 lagging from a 480 V (line-to-line), 50 Hz supply. A three-phase capacitor bank in parallel with the load must raise the overall power factor to 0.92 lagging. The real power stays the same. The capacitors are connected in Y. Find the capacitance Cph of each capacitor in µF.

P = 300 kWpf1 = 0.7pf2 = 0.92VL = 480 Vf = 50 Hz
Cph = µF
3.TransformersMedium
10 Ω41

A 10 Ω resistor is connected across the secondary winding of an ideal transformer with a turns ratio N₁:N₂ = 4:1. Find the resistance R1′ seen looking into the primary winding.

N1:N2 = 4:1RL = 10 Ω
R1′ = Ω
4.TransformersHard
pf 0.95500 kVA, η = 96.5%

A single-phase 500 kVA transformer has a core loss of 2500 W. At rated load and a power factor of 0.95 lagging its efficiency is 96.5%. Find the full-load copper loss Pcu,fl in watts.

S = 500 kVAPcore = 2500 Wpf = 0.95η = 96.5%
Pcu,fl = W
5.AC power & power factorMedium
P = 5 kWQSφ

A single-phase motor takes 5 kW at a power factor of 0.75 lagging from a 240 V supply. Find the line current I.

P = 5 kWpf = 0.75V = 240 V
I = A
6.AC power & power factorHard
P = 20 kWQ1​S1​φ1​QC​

A single-phase load takes 20 kW at a power factor of 0.7 lagging from a 230 V, 60 Hz supply. A capacitor connected in parallel raises the power factor to 0.95. Find the new line current Inew.

P = 20 kWpf1 = 0.7pf2 = 0.95V = 230 Vf = 60 Hz
Inew = A
7.AC impedance & phasorsMedium
12 V60 HzR = 40 ΩL = 50 mHI

A resistor and an inductor are connected in parallel across a 12 V (rms), 60 Hz supply. Find the rms current I.

V = 12 V (rms)f = 60 HzR = 40 ΩL = 50 mH
I = A
8.AC impedance & phasorsHard
50 V500 HzR1​ = 50 ΩR2​ = 20 ΩC = 22 µF

A resistor R1 is connected in series with a parallel combination of R2 and a capacitor C, across a 50 V (rms), 500 Hz supply. Find the magnitude of the impedance |Z|.

V = 50 V (rms)f = 500 HzR1 = 50 ΩR2 = 20 ΩC = 22 µF
|Z| = Ω
9.DC motorsMedium
T (N·m)n (rpm)n0​ = ?

A DC motor with k = 0.8 V·s/rad runs from 240 V. Neglecting all losses at no load, find its no-load speed n0 in rpm.

V = 240 Vk = 0.8 V·s/rad
n0 = rpm
10.DC motorsHard
+−220 VD = ?Ra​ = 0.4 ΩM+−En = 800 rpmT = 15 N·m

A DC chopper feeds a motor (k = 1 V·s/rad, Ra = 0.4 Ω) from a 220 V DC bus. The average armature voltage is D·220 V. Find the duty cycle D that runs the motor at 800 rpm with a load of 15 N·m.

Vdc = 220 Vk = 1 V·s/radRa = 0.4 ΩT = 15 N·mn = 800 rpm
D = %

3Solutions

1.Three-phase power

Answer: P = 21.95 kW

Balanced three-phase systems: in a Y (star) connection the line-to-line voltage is √3 times the phase voltage, VL = √3·Vph, and the line current equals the phase current. In a Δ (delta) connection the line-to-line voltage equals the phase voltage and the line current is √3 times the phase current, IL = √3·Iph. The total power is three times the power of one phase: P = 3·Vph·Iph·cos φ = √3·VL·IL·cos φ.

Apparent power

S = √3·VL·IL = √3·480·30 = 24.94 kVA

Real power

P = S·cos φ = 24.94·0.88 = 21.95 kW

Answer

P = 21.95 kW
2.Three-phase power

Answer: Cph = 2463 µF

Balanced three-phase systems: in a Y (star) connection the line-to-line voltage is √3 times the phase voltage, VL = √3·Vph, and the line current equals the phase current. In a Δ (delta) connection the line-to-line voltage equals the phase voltage and the line current is √3 times the phase current, IL = √3·Iph. The total power is three times the power of one phase: P = 3·Vph·Iph·cos φ = √3·VL·IL·cos φ. Power factor correction: capacitors supply reactive power locally, QC = P·(tan φ1 − tan φ2). Each of the three capacitors supplies QC/3 = V²·ω·C, where V is the voltage across that capacitor: VL in a Δ bank, VL/√3 in a Y bank.

Reactive power before and after

The real power is unchanged, so each power factor fixes the reactive power: Q = P·tan φ.

Q1 = 300·tan(acos 0.7) = 300·1.02 = 306.1 kvar
Q2 = 300·tan(acos 0.92) = 300·0.426 = 127.8 kvar

Reactive power from the capacitors

QC = Q1 − Q2 = 178.3 kvar

Capacitance per phase

In a Y bank each capacitor is connected between a line and the star point.

V = 480/√3 = 277.1 V, ω = 2π·50 = 314.2 rad/s
Cph = (QC/3)/(ω·V²) = 59421/(314.2·277.1²) = 2463 µF

Answer

Cph = 2463 µF
3.Transformers

Answer: R1′ = 160 Ω

Ideal transformer: the voltages are in the ratio of the turns and the currents in the inverse ratio: V₁/V₂ = N₁/N₂ = a and I₁/I₂ = N₂/N₁ = 1/a, so the power in equals the power out, V₁·I₁ = V₂·I₂. A load impedance Z on the secondary looks like a²·Z from the primary.

Referred resistance

The voltage goes up by a and the current down by a, so the ratio V/I goes up by a².

R1′ = a²·RL = 4²·10 = 160 Ω

Answer

R1′ = 160 Ω
4.Transformers

Answer: Pcu,fl = 14728 W

Transformer losses: the core loss (hysteresis and eddy currents) depends on the voltage and is the same at any load. The copper loss in the windings goes with the current squared, so at a fraction x of rated load it is x²·Pcu,fl. Efficiency η = Pout/(Pout + Pcore + Pcu), with Pout = x·S·pf. The efficiency is highest at the load where the copper loss equals the core loss.

Output and input power

Pout = 500·0.95 = 475 kW
Pin = 475000/0.965 = 492228 W

Total and copper losses

Ploss = 492228 − 475000 = 17228 W
Pcu,fl = 17228 − 2500 = 14728 W

Answer

Pcu,fl = 14728 W
5.AC power & power factor

Answer: I = 27.78 A

AC power: apparent power S = V·I (VA) splits into real power P = S·cos φ (W), which does useful work, and reactive power Q = S·sin φ (var), which moves back and forth between source and load. The power factor is cos φ. A capacitor in parallel supplies reactive power locally, so the line current drops for the same real power.

Line current

Only the real part of the power does work, so divide by the power factor.

I = P/(V·cos φ) = 5000/(240·0.75) = 27.78 A

Answer

I = 27.78 A
6.AC power & power factor

Answer: Inew = 91.53 A

AC power: apparent power S = V·I (VA) splits into real power P = S·cos φ (W), which does useful work, and reactive power Q = S·sin φ (var), which moves back and forth between source and load. The power factor is cos φ. A capacitor in parallel supplies reactive power locally, so the line current drops for the same real power.

Reactive power before and after

The real power P does not change; only the reactive power drawn from the supply does.

Q1 = P·tan φ1 = 20·tan(45.57°) = 20.4 kvar
Q2 = P·tan φ2 = 20·tan(18.19°) = 6.574 kvar
QC = Q1 − Q2 = 13.83 kvar

New line current

Inew = P/(V·cos φ2) = 20000/(230·0.95) = 91.53 A

Answer

Inew = 91.53 A
7.AC impedance & phasors

Answer: I = 0.7038 A

AC circuits with phasors: resistors, inductors and capacitors have impedances R, jωL and 1/(jωC), with ω = 2πf. In series, impedances add like resistances, but as complex numbers. Rms current and voltage follow Ohm’s law with |Z|.

Reactance

XL = ωL = 2π·60·0.05 = 18.85 Ω

Branch currents

Both branches are connected straight across the supply, so each sees the full voltage V.

IR = V/R = 12/40 = 0.3 A
IX = V/XL = 12/18.85 = 0.6366 A

Total current

The resistor current is in phase with V and the reactive current is 90° out of phase, so they add like the sides of a right triangle.

I = √(IR² + IX²) = √(0.3² + 0.6366²) = 0.7038 A

Answer

I = 0.7038 A
8.AC impedance & phasors

Answer: |Z| = 57.66 Ω

AC circuits with phasors: resistors, inductors and capacitors have impedances R, jωL and 1/(jωC), with ω = 2πf. In series, impedances add like resistances, but as complex numbers. Rms current and voltage follow Ohm’s law with |Z|.

Reactance

XC = 1/(2π·500·22·10⁻⁶) = 14.47 Ω

Parallel combination

Multiply top and bottom by the complex conjugate to split Zp into real and imaginary parts.

Zp = R₂·(−jXC)/(R₂ − jXC) = (R₂·XC² − jR₂²·XC)/(R₂² + XC²)
Zp = 6.871 − j9.498 Ω

Total impedance

Z = 50 + 6.871 − j9.498 = 56.87 − j9.498 Ω
|Z| = √(56.87² + 9.498²) = 57.66 Ω

Answer

|Z| = 57.66 Ω
9.DC motors

Answer: n0 = 2865 rpm

DC motor: the armature is a resistance Ra in series with the back-EMF E, so V = E + Ia·Ra. The back-EMF grows with speed, E = k·ω, and the torque with current, T = k·Ia, with the same motor constant k (V·s/rad = N·m/A) in SI units. Convert speeds with ω = 2π·n/60. The developed power is E·Ia = T·ω; the input power is V·Ia, and the copper loss Ia²Ra and the rotational loss make the difference. The speed falls in a straight line with torque, ω = V/k − Ra·T/k², from the no-load speed V/k to zero at the stall torque k·V/Ra. At standstill E = 0, so the starting current V/Ra is large unless a resistor limits it.

No-load speed

ω₀ = V/k = 240/0.8 = 300 rad/s
n0 = 60·300/(2π) = 2865 rpm

Answer

n0 = 2865 rpm
10.DC motors

Answer: D = 40.81 %

DC motor: the armature is a resistance Ra in series with the back-EMF E, so V = E + Ia·Ra. The back-EMF grows with speed, E = k·ω, and the torque with current, T = k·Ia, with the same motor constant k (V·s/rad = N·m/A) in SI units. Convert speeds with ω = 2π·n/60. The developed power is E·Ia = T·ω; the input power is V·Ia, and the copper loss Ia²Ra and the rotational loss make the difference. The speed falls in a straight line with torque, ω = V/k − Ra·T/k², from the no-load speed V/k to zero at the stall torque k·V/Ra. At standstill E = 0, so the starting current V/Ra is large unless a resistor limits it.

Required armature voltage

Va = 1·83.78 + 15·0.4 = 89.78 V

Duty cycle

D = 89.78/220 = 40.81 %

Answer

D = 40.81 %

ExamProblems · examproblems.com/courses/power-systems