A voltmeter, an ammeter and a wattmeter connected to a single-phase inductive load read 230 V, 3.5 A and 483 W. Find the reactive power Q taken by the load.
AC power & power factor worksheet with answers
A voltmeter, an ammeter and a wattmeter connected to a single-phase inductive load read 230 V, 20 A and 4140 W. Find the reactive power Q taken by the load.
Two loads are connected in parallel to a 400 V single-phase supply: a 3 kW load at a power factor of 0.65 lagging and a 28 kW load at a power factor of 0.9 lagging. Find the total current I drawn from the supply.
A single-phase motor takes 39 kW at a power factor of 0.8 lagging from a 230 V supply. Find the reactive power Q it draws.
A single-phase load takes 25 kW at a power factor of 0.7 lagging from a 240 V, 60 Hz supply. A capacitor connected in parallel raises the power factor to 0.95. Find the capacitance C needed.
A single-phase load takes 15 kW at a power factor of 0.65 lagging from a 240 V, 50 Hz supply. A capacitor connected in parallel raises the power factor to 0.95. Find the reactive power QC the capacitor must supply.
Answer key
- 1. Q = 644 var
- 2. Q = 2005 var
- 3. I = 88.47 A
- 4. Q = 29.25 kvar
- 5. C = 796.1 µF
- 6. QC = 12.61 kvar