A single-phase load draws 16 A (rms) from a 240 V (rms) supply at a power factor of 0.6 lagging. Find the real power P it takes.
AC power & power factor worksheet with answers
A voltmeter, an ammeter and a wattmeter connected to a single-phase inductive load read 240 V, 13.5 A and 2754 W. Find the reactive power Q taken by the load.
A single-phase motor takes 8 kW at a power factor of 0.6 lagging from a 230 V supply. Find the line current I.
Two loads are connected in parallel to a 400 V single-phase supply: a 19 kW load at a power factor of 0.7 lagging and a 15 kW load at a power factor of 0.7 leading. Find the overall power factor cos φ seen by the supply.
A single-phase load takes 30 kW at a power factor of 0.75 lagging from a 400 V, 60 Hz supply. A capacitor connected in parallel raises the power factor to 0.92. Find the reactive power QC the capacitor must supply.
A single-phase load takes 10 kW at a power factor of 0.6 lagging from a 400 V, 50 Hz supply. A 100 µF capacitor is connected in parallel with the load. Find the new line current I.
Answer key
- 1. P = 2304 W
- 2. Q = 1707 var
- 3. I = 57.97 A
- 4. cos φ = 0.9929
- 5. QC = 13.68 kvar
- 6. I = 32.5 A