A load takes 19.5 kW of real power and 10 kvar of reactive power (lagging). Find the apparent power S.
AC power & power factor worksheet with answers
A load takes 47 kW of real power and 12 kvar of reactive power (lagging). Find the power factor cos φ.
A single-phase motor takes 16 kW at a power factor of 0.9 lagging from a 230 V supply. Find the line current I.
A load with impedance Z = 5 + j12 Ω is connected to a 240 V (rms) single-phase supply. Find the apparent power S.
A single-phase load takes 20 kW at a power factor of 0.75 lagging from a 240 V, 60 Hz supply. A capacitor connected in parallel raises the power factor to 0.92. Find the capacitance C needed.
A single-phase load takes 30 kW at a power factor of 0.8 lagging from a 230 V, 60 Hz supply. A capacitor connected in parallel raises the power factor to 0.9. Find the new line current Inew.
Answer key
- 1. S = 21.91 kVA
- 2. cos φ = 0.9689
- 3. I = 77.29 A
- 4. S = 4431 VA
- 5. C = 419.9 µF
- 6. Inew = 144.9 A