A voltmeter, an ammeter and a wattmeter connected to a single-phase inductive load read 230 V, 19.5 A and 2691 W. Find the power factor cos φ of the load.
AC power & power factor worksheet with answers
A single-phase load draws 18 A (rms) from a 240 V (rms) supply at a power factor of 0.85 lagging. Find the real power P it takes.
Two loads are connected in parallel to a 230 V single-phase supply: a 2 kW load at a power factor of 0.85 lagging and a 22 kW load at a power factor of 0.8 lagging. Find the overall power factor cos φ seen by the supply.
A single-phase motor takes 8 kW at a power factor of 0.8 lagging from a 230 V supply. Find the line current I.
A 120 V (rms), 50 Hz source has an internal impedance Zs = 20 + j30 Ω. The load impedance ZL can be chosen freely. Find the maximum real power Pmax that can be delivered to the load.
A single-phase load takes 30 kW at a power factor of 0.75 lagging from a 230 V, 50 Hz supply. A capacitor connected in parallel raises the power factor to 0.98. Find the capacitance C needed.
Answer key
- 1. cos φ = 0.6
- 2. P = 3672 W
- 3. cos φ = 0.8042
- 4. I = 43.48 A
- 5. Pmax = 180 W
- 6. C = 1225 µF
Full step-by-step solutions: practise this topic on examproblems.com.