A load takes 40 kW of real power and 23.5 kvar of reactive power (lagging). Find the power factor cos φ.
AC power & power factor worksheet with answers
A single-phase load connected to a 400 V supply takes 12 kW and 13.5 kvar. Find the current I drawn from the supply.
A single-phase motor takes 7 kW at a power factor of 0.9 lagging from a 240 V supply. Find the line current I.
Two loads are connected in parallel to a 230 V single-phase supply: a 26 kW load at a power factor of 0.65 lagging and a 21 kW load at a power factor of 0.95 lagging. Find the total current I drawn from the supply.
A 200 kVA single-phase transformer supplies a load of 54 kW at a power factor of 0.8 lagging. How much extra real power ΔP can be added as a resistive (unity power factor) load before the transformer reaches its kVA rating?
A single-phase load takes 45 kW at a power factor of 0.65 lagging from a 230 V, 50 Hz supply. A capacitor connected in parallel raises the power factor to 0.9. Find the reactive power QC the capacitor must supply.
Answer key
- 1. cos φ = 0.8622
- 2. I = 45.16 A
- 3. I = 32.41 A
- 4. I = 260.9 A
- 5. ΔP = 141.9 kW
- 6. QC = 30.82 kvar