A voltmeter, an ammeter and a wattmeter connected to a single-phase inductive load read 240 V, 9.5 A and 1482 W. Find the reactive power Q taken by the load.
AC power & power factor worksheet with answers
A load takes 35.5 kW of real power and 44 kvar of reactive power (lagging). Find the power factor cos φ.
A single-phase motor takes 40 kW at a power factor of 0.9 lagging from a 400 V supply. Find the reactive power Q it draws.
A single-phase motor takes 9 kW at a power factor of 0.65 lagging from a 240 V supply. Find the line current I.
A single-phase load takes 15 kW at a power factor of 0.6 lagging from a 240 V, 50 Hz supply. A capacitor connected in parallel raises the power factor to 0.98. Find the reactive power QC the capacitor must supply.
A single-phase load takes 10 kW at a power factor of 0.6 lagging from a 240 V, 60 Hz supply. A 220 µF capacitor is connected in parallel with the load. Find the new power factor cos φ seen by the supply.
Answer key
- 1. Q = 1733 var
- 2. cos φ = 0.6279
- 3. Q = 19.37 kvar
- 4. I = 57.69 A
- 5. QC = 16.95 kvar
- 6. cos φ = 0.7598