A load takes 35.5 kW of real power and 23.5 kvar of reactive power (lagging). Find the power factor cos φ.
AC power & power factor worksheet with answers
A single-phase load draws 17 A (rms) from a 120 V (rms) supply at a power factor of 0.6 lagging. Find the real power P it takes.
A single-phase motor takes 11 kW at a power factor of 0.7 lagging from a 230 V supply. Find the line current I.
A load with impedance Z = 16 + j12 Ω is connected to a 120 V (rms) single-phase supply. Find the reactive power Q it absorbs.
A 100 kVA single-phase transformer supplies a load of 58 kW at a power factor of 0.85 lagging. How much extra real power ΔP can be added as a resistive (unity power factor) load before the transformer reaches its kVA rating?
A single-phase load takes 20 kW at a power factor of 0.8 lagging from a 400 V, 60 Hz supply. A capacitor connected in parallel raises the power factor to 0.92. Find the new line current Inew.
Answer key
- 1. cos φ = 0.8339
- 2. P = 1224 W
- 3. I = 68.32 A
- 4. Q = 432 var
- 5. ΔP = 35.32 kW
- 6. Inew = 54.35 A