A single-phase load draws 2 A (rms) from a 120 V (rms) supply at a power factor of 0.9 lagging. Find the real power P it takes.
AC power & power factor worksheet with answers
A voltmeter, an ammeter and a wattmeter connected to a single-phase inductive load read 240 V, 16 A and 3648 W. Find the power factor cos φ of the load.
An inductive load takes 11.5 A and 2484 W from a 240 V (rms) single-phase supply. Model it as a resistance R in series with a reactance X. Find R.
A single-phase motor takes 6 kW at a power factor of 0.8 lagging from a 240 V supply. Find the reactive power Q it draws.
A 50 V (rms), 1000 Hz source has an internal impedance Zs = 4 + j15 Ω. The load impedance ZL can be chosen freely. Find the maximum real power Pmax that can be delivered to the load.
A single-phase load takes 10 kW at a power factor of 0.7 lagging from a 230 V, 50 Hz supply. A capacitor connected in parallel raises the power factor to 0.9. Find the capacitance C needed.
Answer key
- 1. P = 216 W
- 2. cos φ = 0.95
- 3. R = 18.78 Ω
- 4. Q = 4.5 kvar
- 5. Pmax = 156.3 W
- 6. C = 322.5 µF
Full step-by-step solutions: practise this topic on examproblems.com.