A voltmeter, an ammeter and a wattmeter connected to a single-phase inductive load read 240 V, 9 A and 1512 W. Find the power factor cos φ of the load.
AC power & power factor worksheet with answers
A single-phase load connected to a 400 V supply takes 17.5 kW and 17 kvar. Find the current I drawn from the supply.
A single-phase motor takes 20 kW at a power factor of 0.7 lagging from a 230 V supply. Find the reactive power Q it draws.
A single-phase motor takes 28 kW at a power factor of 0.85 lagging from a 240 V supply. Find the line current I.
A single-phase load takes 15 kW at a power factor of 0.65 lagging from a 230 V, 50 Hz supply. A capacitor connected in parallel raises the power factor to 0.95. Find the reactive power QC the capacitor must supply.
A single-phase load takes 5 kW at a power factor of 0.6 lagging from a 230 V, 50 Hz supply. A capacitor connected in parallel raises the power factor to 0.92. Find the new line current Inew.
Answer key
- 1. cos φ = 0.7
- 2. I = 60.99 A
- 3. Q = 20.4 kvar
- 4. I = 137.3 A
- 5. QC = 12.61 kvar
- 6. Inew = 23.63 A