A single-phase load draws 8 A (rms) from a 400 V (rms) supply at a power factor of 0.65 lagging. Find the reactive power Q it takes.
AC power & power factor worksheet with answers
A single-phase load connected to a 120 V supply takes 14.5 kW and 17.5 kvar. Find the current I drawn from the supply.
A single-phase motor takes 32 kW at a power factor of 0.8 lagging from a 230 V supply. Find the line current I.
A load with impedance Z = 16 + j12 Ω is connected to a 230 V (rms) single-phase supply. Find the reactive power Q it absorbs.
A 120 V (rms), 50 Hz source has an internal impedance Zs = 4 + j30 Ω. The load impedance ZL can be chosen freely. Find the maximum real power Pmax that can be delivered to the load.
A 230 V (rms), 1000 Hz source has an internal impedance Zs = 5 + j10 Ω. The load impedance ZL can be chosen freely. The load for maximum power is built from a resistor in series with a capacitor. Find the capacitance C.
Answer key
- 1. Q = 2432 var
- 2. I = 189.4 A
- 3. I = 173.9 A
- 4. Q = 1587 var
- 5. Pmax = 900 W
- 6. C = 15.92 µF